ALARM 85, Dang fail PB:
Profibus/Profisafe Error.
WARNING/ALARM 104, Mixing fan fault
The fan monitor checks that the fan is spinning at power-
up or whenever the mixing fan is turned on. If the fan is
not operating, then the fault is annunciated. The mixing-
fan fault can be configured as a warning or an alarm trip
by
14-53 Fan Monitor
.
Troubleshooting Cycle power to the frequency converter
to determine if the warning/alarm returns.
ALARM 243, Brake IGBT
This alarm is only for F Frame frequency converters. It is
equivalent to Alarm 27. The report value in the alarm log
indicates which power module generated the alarm:
1 = left most inverter module.
2 = middle inverter module in F12 or F3 frame
sizes.
2 = right inverter module in F10 or F11 frame
sizes.
2 = second frequency converter from the left
inverter module in F14 frame size.
3 = right inverter module in F12 or F13 frame
sizes.
3 = third from the left intverter module in F14
frame size.
4 = far right inverter module in F14 frame size.
5 = rectifier module.
6 = right rectifier module in F14 frame size.
ALARM 244, Heatsink temperature
This alarm is only for F Frame frequency converters. It is
equivalent to Alarm 29. The report value in the alarm log
indicates which power module generated the alarm.
1 = left most inverter module.
2 = middle inverter module in F12 or F3 frame
sizes.
2 = right inverter module in F10 or F11 frame
sizes.
2 = second frequency converter from the left
inverter module in F14 frame size.
3 = right inverter module in F12 or F13 frame
sizes.
3 = third from the left intverter module in F14
frame size.
4 = far right inverter module in F14 frame size.
5 = rectifier module.
6 = right rectifier module in F14 frame size.
ALARM 245, Heatsink sensor
This alarm is only for F Frame frequency converters. It is
equivalent to Alarm 39. The report value in the alarm log
indicates which power module generated the alarm
1 = left most inverter module.
2 = middle inverter module in F12 or F3 frame
sizes.
2 = right inverter module in F10 or F11 frame
sizes.
2 = second frequency converter from the left
inverter module in F14 frame size.
3 = right inverter module in F12 or F13 frame
sizes.
3 = third from the left intverter module in F14
frame size.
4 = far right inverter module in F14 frame size.
5 = rectifier module.
6 = right rectifier module in F14 frame size.
ALARM 246, Power card supply
This alarm is only for F Frame frequency converter. It is
equivalent to Alarm 46. The report value in the alarm log
indicates which power module generated the alarm
1 = left most inverter module.
2 = middle inverter module in F12 or F3 frame
sizes.
2 = right inverter module in F10 or F11 frame
sizes.
2 = second frequency converter from the left
inverter module in F14 frame size.
3 = right inverter module in F12 or F13 frame
sizes.
3 = third from the left intverter module in F14
frame size.
4 = far right inverter module in F14 frame size.
5 = rectifier module.
6 = right rectifier module in F14 frame size.
ALARM 247, Power card temperature
This alarm is only for F Frame frequency converter. It is
equivalent to Alarm 69. The report value in the alarm log
indicates which power module generated the alarm
1 = left most inverter module.
2 = middle inverter module in F12 or F3 frame
sizes.
2 = right inverter module in F10 or F11 frame
sizes.
2 = second frequency converter from the left
inverter module in F14 frame size.
Warnings and Alarms
VLT
®
AutomationDrive Operating
Instructions
MG33AM02 - VLT
®
is a registered Danfoss trademark
59
8
8
Содержание FC 300
Страница 1: ...MAKING MODERN LIVING POSSIBLE Operating Instructions VLT AutomationDrive FC 300 0 25 75 kW...
Страница 2: ......
Страница 4: ...Safety VLT AutomationDrive Operating Instructions MG33AM02 VLT is a registered Danfoss trademark...
Страница 99: ...Index VLT AutomationDrive Operating Instructions MG33AM02 VLT is a registered Danfoss trademark 95...
Страница 100: ...www danfoss com drives MG33AM02 130R0300 MG33AM02 Rev 2012 11 02...