LCP and typical control card power consumptions are included. Further options and customer load may add up to 30W to the losses.
(Though typical only 4W extra for a fully loaded control card, or options for slot A or slot B, each).
Although measurements are made with state of the art equipment, some measurement inaccuracy must be allowed for (
±
5%).
5) The three values for the max. cable cross section are for single core, flexible wire and flexible wire with sleeve, respectively.
PK75
P1K1
P1K5
P2K2
P3K0
P4K0
P5K5
P7K5
Typical Shaft Output [kW]
0.75
1.1
1.5
2.2
3
4
5.5
7.5
Enclosure IP20, IP21
A3
A3
A3
A3
A3
A3
A3
A3
Enclosure IP55
A5
A5
A5
A5
A5
A5
A5
A5
Output current
Continuous (3x525-550 V) [A]
1.8
2.6
2.9
4.1
5.2
6.4
9.5
11.5
Intermittent (3x525-550 V) [A]
2.9
4.2
4.6
6.6
8.3
10.2
15.2
18.4
Continuous (3x551-600 V) [A]
1.7
2.4
2.7
3.9
4.9
6.1
9.0
11.0
Intermittent (3x551-600 V) [A]
2.7
3.8
4.3
6.2
7.8
9.8
14.4
17.6
Continuous kVA (525 V AC) [kVA]
1.7
2.5
2.8
3.9
5.0
6.1
9.0
11.0
Continuous kVA (575 V AC) [kVA]
1.7
2.4
2.7
3.9
4.9
6.1
9.0
11.0
Max. input current
Continuous (3x525-600 V) [A]
1.7
2.4
2.7
4.1
5.2
5.8
8.6
10.4
Intermittent (3x525-600 V) [A]
2.7
3.8
4.3
6.6
8.3
9.3
13.8
16.6
Additional specifications
IP20, IP21 max. cable cross section
5)
(mains,
motor, brake and load sharing) [mm
2
(AWG)]
2)
4,4,4 (12,12,12)
(min. 0.2 (24))
IP55, IP66 max. cable cross section
5)
(mains,
motor, brake and load sharing) [mm
2
(AWG)]
4,4,4 (12,12,12)
Max. cable cross section
5)
with disconnect
6,4,4 (10,12,12)
Estimated power loss
at rated max. load [W]
4)
35
50
65
92
122
145
195
261
Weight, Enclosure IP20 [kg]
6.5
6.5
6.5
6.5
6.5
6.5
6.6
6.6
Weight, enclosure IP55 [kg]
13.5
13.5
13.5
13.5
13.5
13.5
14.2
14.2
Efficiency
4)
0.97
0.97
0.97
0.97
0.97
0.97
0.97
0.97
Table 10.7 Mains Supply 3x525-600 V AC (FC 302 only)
Specifications
VLT
®
AutomationDrive Operating
Instructions
70
MG33AM02 - VLT
®
is a registered Danfoss trademark
10
10
Содержание FC 300
Страница 1: ...MAKING MODERN LIVING POSSIBLE Operating Instructions VLT AutomationDrive FC 300 0 25 75 kW...
Страница 2: ......
Страница 4: ...Safety VLT AutomationDrive Operating Instructions MG33AM02 VLT is a registered Danfoss trademark...
Страница 99: ...Index VLT AutomationDrive Operating Instructions MG33AM02 VLT is a registered Danfoss trademark 95...
Страница 100: ...www danfoss com drives MG33AM02 130R0300 MG33AM02 Rev 2012 11 02...