P30K
P37K
P45K
P55K
P75K
High/Normal Load
1)
HO
NO
HO
NO
HO
NO
HO
NO
HO
NO
Typical Shaft output [kW]
30
37
37
45
45
55
55
75
75
90
Enclosure IP20
B4
C3
C3
C4
C4
Enclosure IP21
C1
C1
C1
C2
C2
Enclosure IP55, IP66
C1
C1
C1
C2
C2
Output current
Continuous (3x380-440 V) [A]
61
73
73
90
90
106
106
147
147
177
Intermittent (60 s overload)
(3x380-440 V) [A]
91.5
80.3
110
99
135
117
159
162
221
195
Continuous (3x441-500 V) [A]
52
65
65
80
80
105
105
130
130
160
Intermittent (60 s overload)
(3x441-500 V) [A]
78
71.5
97.5
88
120
116
158
143
195
176
Continuous kVA (400 V AC) [kVA]
42.3
50.6
50.6
62.4
62.4
73.4
73.4
102
102
123
Continuous kVA (460 V AC) [kVA]
51.8
63.7
83.7
104
128
Max. input current
Continuous (3x380-440 V) [A]
55
66
66
82
82
96
96
133
133
161
Intermittent (60 s overload)
(3x380-440 V) [A]
82.5
72.6
99
90.2
123
106
144
146
200
177
Continuous (3x441-500 V) [A]
47
59
59
73
73
95
95
118
118
145
Intermittent (60 s overload)
(3x441-500 V) [A]
70.5
64.9
88.5
80.3
110
105
143
130
177
160
Additional specifications
IP20 max. cable cross-section
5)
(mains and motor)
35 (2)
50 (1)
50 (1)
150 (300 MCM)
150 (300 MCM)
IP20 max. cable cross-section
5)
(brake and load sharing)
35 (2)
50 (1)
50 (1)
95 (4/0)
95 (4/0)
IP21, IP55, IP66 max. cable cross-
section
5)
(mains, motor) [mm
2
(AWG)]
2)
50 (1)
50 (1)
50 (1)
150 (300 MCM)
150 (300MCM)
IP21, IP55, IP66 max. cable cross-
section
5)
(brake, load sharing)
[mm
2
(AWG)]
2)
50 (1)
50 (1)
50 (1)
95 (3/0)
95 (3/0)
Max cable size with mains
disconnect [mm
2
(AWG)]
2)
50, 35, 35
(1, 2, 2)
95, 70, 70
(3/0, 2/0, 2/0)
185, 150, 120
(350 MCM, 300
MCM, 4/0)
Estimated power loss
at rated max. load [W]
4)
570
698
697
843
891
1083
1022
1384
1232
1474
Weight,
enclosure IP21, IP55, IP66 [kg]
45
45
45
65
65
Efficiency
4)
0.98
0.98
0.98
0.98
0.99
Table 10.6 Mains Supply 3x380-500 V AC (FC 302), 3x380-480 V AC (FC 301)
For fuse ratings, see 10.3.1 Fuses
1) High overload = 160% torque during 60 s. Normal overload = 110% torque during 60 s.
2) American Wire Gauge.
3) Measured using 5 m screened motor cables at rated load and rated frequency.
4) The typical power loss is at nominal load conditions and expected to be within
±
15% (tolerence relates to variety in voltage and
cable conditions).
Values are based on a typical motor efficiency (eff2/eff3 border line). Motors with lower efficiency will also add to the power loss in the
frequency converter and opposite.
If the switching frequency is increased compared to the default setting, the power losses may rise significantly.
Specifications
VLT
®
AutomationDrive Operating
Instructions
MG33AM02 - VLT
®
is a registered Danfoss trademark
69
10
10
Содержание FC 300
Страница 1: ...MAKING MODERN LIVING POSSIBLE Operating Instructions VLT AutomationDrive FC 300 0 25 75 kW...
Страница 2: ......
Страница 4: ...Safety VLT AutomationDrive Operating Instructions MG33AM02 VLT is a registered Danfoss trademark...
Страница 99: ...Index VLT AutomationDrive Operating Instructions MG33AM02 VLT is a registered Danfoss trademark 95...
Страница 100: ...www danfoss com drives MG33AM02 130R0300 MG33AM02 Rev 2012 11 02...