10.2 General Technical Data
Mains supply
Supply Terminals (6-Pulse)
L1, L2, L3
Supply Terminals (12-Pulse)
L1-1, L2-1, L3-1, L1-2, L2-2, L3-2
Supply voltage
200-240 V
±
10%
Supply voltage
FC 301: 380-480 V/FC 302: 380-500 V
±
10%
Supply voltage
FC 302: 525-600 V
±
10%
Supply voltage
FC 302: 525-690 V
±
10%
Mains voltage low / mains drop-out:
During low mains voltage or a mains drop-out, the frequency converter continues until the intermediate circuit voltage drops
below the minimum stop level, which corresponds typically to 15% below the frequency converter's lowest rated supply voltage.
Power-up and full torque cannot be expected at mains voltage lower than 10% below the frequency converter's lowest rated
supply voltage.
Supply frequency
50/60 Hz
±
5%
Max. imbalance temporary between mains phases
3.0 % of rated supply voltage
True Power Factor (
λ
)
≥
0.9 nominal at rated load
Displacement Power Factor (cos
ϕ
)
near unity (
>
0.98)
Switching on input supply L1, L2, L3 (power-ups)
≤
7.5 kW
maximum 2 times/min.
Switching on input supply L1, L2, L3 (power-ups) 11-75 kW
maximum 1 time/min.
Switching on input supply L1, L2, L3 (power-ups)
≥
90 kW
maximum 1 time/2 min.
Environment according to EN60664-1
overvoltage category III/pollution degree 2
The unit is suitable for use on a circuit capable of delivering not more than 100,000 RMS symmetrical Amperes, 240/500/600/ 690
V maximum.
Motor output (U, V, W)
Output voltage
0-100% of supply voltage
Output frequency (0.25-75 kW)
FC 301: 0.2-590 Hz/FC 302: 0-590 Hz
Output frequency (90-1000 kW)
0-590
1)
Hz
Output frequency in Flux Mode (FC 302 only)
0-300 Hz
Switching on output
Unlimited
Ramp times
0.01-3600 s
1)
Voltage and power dependent
Torque characteristics
Starting torque (constant torque)
maximum 160% for 60 s
1)
Starting torque
maximum 180% up to 0.5 s
1)
Overload torque (constant torque)
maximum 160% for 60 s
1)
Starting torque (variable torque)
maximum 110% for 60 s
1)
Overload torque (variable torque)
maximum 110% for 60 s
Torque rise time in VVC
plus
(independent of fsw)
10 ms
Torque rise time in FLUX (for 5 kHz fsw)
1 ms
1)
Percentage relates to the nominal torque.
2)
The torque response time depends on application and load but as a general rule, the torque step from 0 to reference is 4-5 x
torque rise time.
Digital inputs
Programmable digital inputs
FC 301: 4 (5)
1)
/FC 302: 4 (6)
1)
Terminal number
18, 19, 27
1)
, 29
1)
, 32, 33,
Logic
PNP or NPN
Voltage level
0 - 24 V DC
Voltage level, logic'0' PNP
< 5 V DC
Voltage level, logic'1' PNP
> 10 V DC
Voltage level, logic '0' NPN
2)
> 19 V DC
Voltage level, logic '1' NPN
2)
< 14 V DC
Specifications
VLT
®
AutomationDrive Operating
Instructions
MG33AM02 - VLT
®
is a registered Danfoss trademark
77
10
10
Содержание FC 300
Страница 1: ...MAKING MODERN LIVING POSSIBLE Operating Instructions VLT AutomationDrive FC 300 0 25 75 kW...
Страница 2: ......
Страница 4: ...Safety VLT AutomationDrive Operating Instructions MG33AM02 VLT is a registered Danfoss trademark...
Страница 99: ...Index VLT AutomationDrive Operating Instructions MG33AM02 VLT is a registered Danfoss trademark 95...
Страница 100: ...www danfoss com drives MG33AM02 130R0300 MG33AM02 Rev 2012 11 02...