Analog Input (X42/1)
Variable
name:
SNVT
type:
Value:
nvo109AnIn1
Changeable
Min.
Max.
Resolution:
SNVT_volt
0 V
10 V
0.1 V
SNVT_temp_p
-273.15 °C
327.66 °C
0.01 °C
SNVT_lev_percent
0 %
100 %
0,1 %
Analog Input (X42/3)
Variable
name:
SNVT
type:
Value:
nvo109AnIn2
Changeable
Min.
Max.
Resolution:
SNVT_volt
0 V
10 V
0.1 V
SNVT_temp_p
-273.15 °C
327.66 °C
0.01 °C
SNVT_lev_percent
0 %
100 %
0,1 %
Analog Input (X42/5)
Variable
name:
SNVT
type:
Value:
nvo109AnIn3
Changeable
Min.
Max.
Resolution:
SNVT_volt
0 V
10 V
0.1 V
SNVT_temp_p
-273.15 °C
327.66 °C
0.01 °C
SNVT_lev_percent
0 %
100 %
0,1 %
These variables contain the value allocated to the analog input terminal X42/1-5 of the
Analog I/O option, MCB109
. The variable type is changeable with
the commissioning tool.
NB!
This variable is available only if the Analog I/O option (MCB109) has been installed.
5 Configuration of the system