4.1.3 Network Termination
Dependent on the type of topology, at least one of the connected nodes must be terminated (52.5
Ω
). The option has two built-in termination circuits
which are activated by the terminator switches S300 and S301.
If termination is provided elsewhere in the network, the termination switches should be OFF. If a double-terminated bus topology is used, the first and
the last node should be double-terminated (105
Ω
).
Termination switch positions are shown in the table below.
Termination type
S 300
S 301
No termination (factory setting)
OFF
OFF
Double termination (105
Ω
)
ON
OFF
Single termination (52.5
Ω
)
ON
ON
4 How to install
VLT® FC 100 LonWorks
12
MG.11.E2.02 - VLT
®
is a registered Danfoss trademark
4