Reference [%]
Variable
name:
SNVT
type:
Value:
nviRefPcnt
SNVT_lev_percent
Min.
Max.
Resolution:
-163.840 %
+163.830 %
0.005 %
This variable sends the speed reference to the frequency converter. It represents a percentage of the reference range of the frequency converter.
In closed loop operation the reference is interpreted as the setpoint.
Reference [Hz]
Variable
name:
SNVT
type:
Value:
nviRefHz
SNVT_freq_hz
Min.:
Max.:
Resulution:
0.0 Hz
6,553.5 Hz
0.1 Hz
This variable sends the speed reference to the frequency converter in Hz, in open loop mode.
In closed loop mode it is used as the Set-point.
Closed Loop Set-point 1-3
Variable
name:
SNVT
type:
Value:
nviSetpoint1-3
SNVT_lev_percent
Min.:
Max.:
Resulution:
-163.840 %
163.830 %
0.005 %
This variable sends up to 3 different set-points to the frequency converter via the bus.
NB!
Please refer to section
Reference Handling
for more information
Bus Feedback 1-3
Variable
name:
SNVT
type:
Value:
nviFeedback1-3
SNVT_lev_percent
Min.:
Max.:
Resulution:
-163.840 %
163.830 %
0.005 %
This variable sends up to 3 different feedback signals to the frequency converter via the bus.
NB!
For more information on how to manage multiple set-points and feedback sources, please refer to
VLT HVAC Drive Programing Guide
MG.11.BX.YY
.
VLT® FC 100 LonWorks
5 Configuration of the system
MG.11.E2.02 - VLT
®
is a registered Danfoss trademark
23
5
Содержание FC 100
Страница 5: ...2 Safety VLT FC 100 LonWorks 4 MG 11 E2 02 VLT is a registered Danfoss trademark 2...
Страница 11: ...4 How to install VLT FC 100 LonWorks 10 MG 11 E2 02 VLT is a registered Danfoss trademark 4...
Страница 19: ...5 Configuration of the system VLT FC 100 LonWorks 18 MG 11 E2 02 VLT is a registered Danfoss trademark 5...
Страница 57: ...9 Troubleshooting VLT FC 100 LonWorks 56 MG 11 E2 02 VLT is a registered Danfoss trademark 9...