These variables contain the value allocated to the analog output terminal X42/7-11 of the
Analog I/O option
. The variable type is changeable with the
commissioning tool.
NB!
This variable is available only if the Analog I/O option (MCB 109) has been installed.
Setting of RTC
Variable
name:
SNVT
type:
Field:
nviTimeStamp
SNVT_time_stamp
Year
Month
Day
Hour
Minute
Second
2000 -3000
0 - 12
0 - 31
0 - 23
0 - 59
0 - 59
Use this input to set the built-in Real Time Clock.
ECB Option Mode
Variable
name:
SNVT
type:
State:
nviECBMode
SNVT_state
Boolean 1 bit x 16
Controls the operation mode of the ECB option. The binary value of this variable is mapped directly into par. 31-00
Bypass Mode
.
[0] Drive
[1] Bypass
ECB Remote By-pass Activation
Variable
name:
SNVT
type:
State:
nviECBActivation
SNVT_state
Boolean 1 bit x 16
Controls the remote activation of the ECB option.
The binary value of this variable is mapped directly into par. 31-90.
[0] Disabled
[1] Enabled
NB!
This input variable applies only if the ECB option is installed in the frequency converter.
Parameter Access Command
Variable
name:
SNVT
type:
Value:
nviParamRequest
SNVT_param_request
These input variables are used for for frequency converter parameter access.
For more information on parameter access, please refer to
How to Access FC 100 Parameters
section.
5 Configuration of the system
VLT® FC 100 LonWorks
26
MG.11.E2.02 - VLT
®
is a registered Danfoss trademark
5
Содержание FC 100
Страница 5: ...2 Safety VLT FC 100 LonWorks 4 MG 11 E2 02 VLT is a registered Danfoss trademark 2...
Страница 11: ...4 How to install VLT FC 100 LonWorks 10 MG 11 E2 02 VLT is a registered Danfoss trademark 4...
Страница 19: ...5 Configuration of the system VLT FC 100 LonWorks 18 MG 11 E2 02 VLT is a registered Danfoss trademark 5...
Страница 57: ...9 Troubleshooting VLT FC 100 LonWorks 56 MG 11 E2 02 VLT is a registered Danfoss trademark 9...