Analog Input (54)
Variable
name:
SNVT
type:
Value:
nvoAnIn1
Changeable
Min.
Max.
Resolution:
SNVT_volt
0 V
10 V
0.1 V
SNVT_amp_mil
0 mA
20 mA
0.1 mA
SNVT_lev_percent
0 %
100 %
0,1 %
This variable contains the value allocated to the analog input terminal 54.
This terminal can either be configured as a voltage input (0-10 V) or as a current input (0-20 mA), depending on the setting of switch S 202. The variable
type is changeable with the commissioning tool in order to match the appropriate unit.
If the variable type of SNVT_lev_percent is selected, the relative scaling is from 0 V/mA to par. 6-21
Terminal 54 High Voltage
or par. 6-23
Terminal 54
High Current
Analog Input (X30/11)
Variable
name:
SNVT
type:
Value:
nvo101AnIn1
Changeable
Min.
Max.
Resolution:
SNVT_volt
0 V
10 V
0.1 V
SNVT_lev_percent
0 %
100 %
0,1 %
This variable contains the value allocated to the analog input terminal X30/11 of the
General Purpose I/O option, MCB101
.
If the variable type of SNVT_lev_percent is selected, the relative scaling is from 0 V to par. 6-31
Terminal X30/11 High Voltage
.
NB!
This variable is available only if the General Purpose I/O option (MCB101) has been installed.
Analog Input (X30/12)
Variable
name:
SNVT
type:
Value:
nvo101AnIn2
Changeable
Min.
Max.
Resolution:
SNVT_volt
0 V
10 V
0.1 V
SNVT_lev_percent
0 %
100 %
0,1 %
This variable contains the value allocated to the analog input terminal X30/12 of the
General Purpose I/O option, MCB101
.
If the variable type of SNVT_lev_percent is selected, the relative scaling is from 0 V to par. 6-41
Terminal X30/12 High Voltage
.
NB!
This variable is available only if the General Purpose I/O option (MCB101) has been installed.
VLT® FC 100 LonWorks
5 Configuration of the system
MG.11.E2.02 - VLT
®
is a registered Danfoss trademark
31
5
Содержание FC 100
Страница 5: ...2 Safety VLT FC 100 LonWorks 4 MG 11 E2 02 VLT is a registered Danfoss trademark 2...
Страница 11: ...4 How to install VLT FC 100 LonWorks 10 MG 11 E2 02 VLT is a registered Danfoss trademark 4...
Страница 19: ...5 Configuration of the system VLT FC 100 LonWorks 18 MG 11 E2 02 VLT is a registered Danfoss trademark 5...
Страница 57: ...9 Troubleshooting VLT FC 100 LonWorks 56 MG 11 E2 02 VLT is a registered Danfoss trademark 9...