9.4.2 Input variables (nvi)
Variable Function
Variable Name
SNVT type
Profile
FC 100 par.
Start/Stop
nviStartStop
SNVT_switch
FC VSD
CTW/reference
Control word
nviControlword
SNVT_state
FC VSD
CTW
Reset fault
nviResetFaut
SNVT_switch
FC VSD
CTW
Reference [%]
nviRefPcnt
SNVT_lev_percent
FC VSD
Reference
Reference [Hz]
nviRefHz
SNVT_freq_hz
FC VSD
Reference
CL Setpoint 1
nviSetpoint1
SNVT_lev_percent
FC VSD
20-21
CL Setpoint 2
nviSetpoint2
SNVT_lev_percent
FC VSD
20-22
CL Setpoint 3
nviSetpoint3
SNVT_lev_percent
FC VSD
20-23
Bus feedback 1
nviFeedback1
SNVT_lev_percent
FC VSD
8-94
Bus feedback 2
nviFeedback2
SNVT_lev_percent
FC VSD
8-95
Bus feedback 3
nviFeedback3
SNVT_lev_percent
FC VSD
8-96
Digital/relay outputs
nviDigiOutput
SNVT_state_64
FC VSD
5-90
Analog output (42)
nviAnOut1
SNVT_lev_percent
FC VSD
6-53
Analog output (X30/8)
nvi101AnOut1
SNVT_lev_percent
FC VSD
6-63
Analog output (X42/7)
nvi109AnOut1
SNVT_lev_percent
FC VSD
26-43
Analog output (X42/9)
nvi109AnOut2
SNVT_lev_percent
FC VSD
26-53
Analog output (X42/11)
nvi109AnOut3
SNVT_lev_percent
FC VSD
26-63
Setting of RTC
nviTimeStamp
SNVT_time_stamp
FC VSD
0-70
ECB option Mode
nviECBMode
SNVT_state
FC VSD
31-00
ECB By-pass activation
nviECBActivation
SNVT_switch
FC VSD
31-19
Parameter access command
nviParamRequest
UNVT_param_request
FC VSD
-
Drive speed setpoint
nviDrvSpeedStpt
SNVT_switch
VSD 6010
CTW / Reference
Standard Node Object
nviRequest
SNVT_obj_request
Node obj.
-
9.4.3 Configuration properties (nci)
Variable function
Variable name
SNVT type
Profile
FC 100
parameter
Max. motor speed [%]
nciMaxSpeed
SNVT_lev_percent
VSD 6010
4-13
Min. motor speed [%]
nciMinSpeed
SNVT_lev_percent
VSD 6010
4-11
Nom. motor speed [RPM]
nciNmlSpeed
SNVT_rpm
VSD 6010
1-25
Nom. motor frequency [Hz]
nciNmlFreq
SNVT_freq_hz
VSD 6010
1-23
Min. ramp-up time [s]
nciRampUpTime
SNVT_time_sec
VSD 6010
3-41
Min. ramp-down time [s]
nciRampDownTime
SNVT_time_sec
VSD 6010
3-42
Heartbeat time [s]
nciSndHrtBt
SNVT_time_sec
VSD 6010
-
Max Send Time (Heartbeat)
nciMaxStsSendT
SNVT_elapsed_tm
Node obj.
-
Min Send Time (Inhibit timer)
nciMinSendT
SNVT_elapsed_tm
Virtual obj.
-
VLT® FC 100 LonWorks
9 Troubleshooting
MG.11.E2.02 - VLT
®
is a registered Danfoss trademark
63
9
Содержание FC 100
Страница 5: ...2 Safety VLT FC 100 LonWorks 4 MG 11 E2 02 VLT is a registered Danfoss trademark 2...
Страница 11: ...4 How to install VLT FC 100 LonWorks 10 MG 11 E2 02 VLT is a registered Danfoss trademark 4...
Страница 19: ...5 Configuration of the system VLT FC 100 LonWorks 18 MG 11 E2 02 VLT is a registered Danfoss trademark 5...
Страница 57: ...9 Troubleshooting VLT FC 100 LonWorks 56 MG 11 E2 02 VLT is a registered Danfoss trademark 9...