Only display parameters selected in par. 0-20 and par. 0-24 can be viewed. It is possible to store
up to 120 samples in the memory for later reference.
Efficient Parameter Set-up for HVAC Ap-
plications
The parameters can easily be set up for the vast majority of the HVAC applications only by using
the
[Quick Set-up]
option.
After pressing [Quick Menu], the different areas in the quick menu are listed. See also illustration
6.1 below and tables Q3-1 to Q3-4 in the following
Function Set-ups
section.
Example of using the Quick Set-up op-
tion
Assume you want to set the ramp-down time
to 100 seconds!
1.
Press [Quick Set-up]. The first
par.
0-01 Language
in Quick Set-up ap-
pears.
2.
Press [
▼
] repeatetly until
par. 3-42
Ramp 1 Ramp-down Time
appears
with the default setting of 20 sec-
onds.
3.
Press [OK].
4.
Use the [
◀
] button to highlight the
3rd digit before the comma.
5.
Change '0' to '1' by using the [
▲
] but-
ton.
6.
Use the [
▶
] button to highlight the
digit '2'.
7.
Change '2' to '0' with the [
▼
] button.
8.
Press [OK].
The new ramp-down time is now set to 100
seconds.
It is recommended to do the set-up in the or-
der listed.
NOTE
A complete description of the
function is found in the param-
eter sections of this Instruction
Manual.
4.1: Quick Menu view.
The QUICK Set-up menu gives access to the
12 most important set-up parameters of the
drive. After programming, the drive will, in
most cases, be ready for operation. The 12
(see footnote) quick menu parameters are
shown in the table below. A complete descrip-
tion of the function is given in the parameter
sections of this manual.
4. How to Program
VLT
®
HVAC DRIVE High Power
Instruction Manual
76
MG.11.F1.22 - VLT
®
is a registered Danfoss trademark.
4
Содержание FC 100 Series
Страница 131: ...7 Annexes VLT HVAC DRIVE High Power Instruction Manual 7 Annexes MG 11 F1 22 VLT is a registered Danfoss trademark 131 7...
Страница 133: ...VLT HVAC DRIVE High Power Instruction Manual 7 Annexes MG 11 F1 22 VLT is a registered Danfoss trademark 133 7...
Страница 134: ...7 Annexes VLT HVAC DRIVE High Power Instruction Manual 134 MG 11 F1 22 VLT is a registered Danfoss trademark 7...
Страница 135: ...VLT HVAC DRIVE High Power Instruction Manual 7 Annexes MG 11 F1 22 VLT is a registered Danfoss trademark 135 7...