3.78: Compact IP 21 (NEMA 1) and IP 54 (NEMA 12) enclosure E1
3.6.3. Grounding
The following basic issues need to be considered when installing an adjustable fre-
quency drive, so as to obtain electromagnetic compatibility (EMC).
•
Safety grounding: Please note that the adjustable frequency drive has a high leakage
current and must be grounded appropriately for safety reasons. Always follow local safety
regulations.
•
High-frequency grounding: Keep the ground wire connections as short as possible.
Connect the different ground systems at the lowest possible conductor impedance. The lowest
possible conductor impedance is obtained by keeping the conductor as short as possible and by
using the greatest possible surface area.
The metal cabinets of the different devices are mounted on the cabinet rear plate using the lowest
possible HF impedance. This prevents having different HF voltages for the individual devices and
prevents the risk of radio interference currents running in connection cables that may be used
between the devices, as radio interference is reduced.
In order to obtain a low HF impedance, use the fastening bolts of the devices as HF connections
to the rear plate. It is necessary to remove insulating paint and the like from the fastening points.
VLT
®
HVAC DRIVE High Power
Instruction Manual
3. How to Install
MG.11.F1.22 - VLT
®
is a registered Danfoss trademark.
55
3
Содержание FC 100 Series
Страница 131: ...7 Annexes VLT HVAC DRIVE High Power Instruction Manual 7 Annexes MG 11 F1 22 VLT is a registered Danfoss trademark 131 7...
Страница 133: ...VLT HVAC DRIVE High Power Instruction Manual 7 Annexes MG 11 F1 22 VLT is a registered Danfoss trademark 133 7...
Страница 134: ...7 Annexes VLT HVAC DRIVE High Power Instruction Manual 134 MG 11 F1 22 VLT is a registered Danfoss trademark 7...
Страница 135: ...VLT HVAC DRIVE High Power Instruction Manual 7 Annexes MG 11 F1 22 VLT is a registered Danfoss trademark 135 7...