The shrink tube must be speci ed for operating temperature range from -40 ºC to 150 ºC. Self gluing shrink tube is
recommended.
Figure 24. Shrink tube
8. Insert the cable through the corresponding hole in the connection box and connect the cable
lug to the connection point. Use spring washer between the cable lug and the connection screw
or nut. Example of the connection is shown in Figure Cable lug connection to connection the box.
Do not tighten the connection at this point to ensure tting of the cable gland.
Make sure that there is at least 10 mm air gap between the cable lug and other metallic structures including the braid of
the cable. If the air gap is smaller, use extra insulation shrink tube to cover the lug.
Figure 25. Cable lug connection to the connection box (example only, the connection box may look
different)
EM-PMI540-T3000
6. Installation
36 |
©
Danfoss | Produced By: Danfoss Power Solutions | November 2018
| BC265857716810en-000103