Application 17, Type 2 Only
EI.65.D4.02
111
System diagram 17B
Two separate heat circuits connected directly to the district heating network and
with mixing via by-pass valves. Hot-water circuit with indirect and continuous
control of storage tank charging system.
Note:
ECL 2000 Type 2 must be used to control this application.
Heat circuit 1
The motor valve M1 controls the flow temperature, which is measured by the sen-
sor S1. The return temperature measured by the sensor S2 can be limited. The cir-
culation pump P1 is running when the reference flow temperature is above 20 °C
or the outdoor temperature is below 2 °C.
Heat circuit 2
The motor valve M2 controls the flow temperature, which is measured by the sen-
sor S4. The return temperature measured by the sensor S5 can be limited. The cir-
culation pump P2 is running when the reference flow temperature is above 20 °C
or the outdoor temperature is below 2 °C.
Hot-water circuit
The motor valve M3 controls the hot-water temperature measured by S10 continu-
ously. The upper and lower storage tank temperatures are measured by the sensors
S6 and S7, respectively. A low S6 temperature causes the charging pump P3 to
start and the pump is stopped when a high temperature is measured at S7. It is pos-
sible to limit the return temperature measured by S11. The pump P4 maintains cir-
culation through the heat exchanger but is not controlled by the ECL 2000.
Содержание ECL 2000
Страница 1: ...Installation Guide ECL 2000 11 99 EI 65 D4 02...
Страница 2: ......
Страница 3: ...Installation Guide ECL 2000 Danfoss A S EI 65 D4 02...
Страница 16: ...Mounting EI 65 D4 02 10...
Страница 26: ...Electrical Connections EI 65 D4 02 20...
Страница 120: ...Application 17 Type 2 Only EI 65 D4 02 114...
Страница 130: ...Appendix C Service Menus EI 65 D4 02 124 C 2 Hot Water Service Menus 0 1 2 3 4 5 1 or or 2 or 3 4 or or...
Страница 131: ...Appendix C Service Menus EI 65 D4 02 125 C 3 Common Function Menus 0 1 2 3 4 5 1 2 etc 3 etc 4 etc...
Страница 132: ...Appendix C Service Menus EI 65 D4 02 126 C 3 Common Function Menus Cont 0 1 2 3 4 5 5 etc 6 7 8 9...
Страница 133: ...Appendix C Service Menus EI 65 D4 02 127 C 3 Common Function Menus Cont 0 1 2 3 4 5 10 11 or or 12 13...
Страница 134: ...Appendix C Service Menus EI 65 D4 02 128...
Страница 136: ...References EI 65 D4 02 130...
Страница 140: ...Index EI 65 D4 02 134...