Appendix A. Specifications
EI.65.D4.02
115
APPENDIX A. SPECIFICATIONS
A.1 General Data
Supply voltage
230 V version:
24 V version:
230 V AC 50 Hz
24 V AC 50 Hz
Power Consumption
5 VA
Voltage range
230 V version:
24 V version:
207 – 244 V AC
21.6 – 26.4 V AC
Cable
Max. 1.5 mm
2
Ambient temperature
0
→
50 °C
Storage temperature
– 40
→
70 °C
Enclosure
144 x 96 mm DIN 43700
EMC Radiation
Complies with: Emission: EN50081-1
Immunity: EN50082-1
Protection class
According to installation:
IP 41 DIN 40050 together with 087B8099
IP 65 DIN 40050 together with 087B3064
Sensor type
Pt 1000 (1000
Ω
at 0 °C)
Fast digital input
1 fast digital input:
2 fast digital inputs:
3 fast digital inputs:
4 fast digital inputs:
0
→
200 Hz
0
→
100 Hz
0
→
66.7 Hz
0
→
50 Hz
Voltage input
0
→
10 V DC
Load on 3-point outputs
230 V version:
24 V version:
0.15 A
1 A
Load on relay outputs
230 V version:
24 V version:
4 (2) A 230 V AC
4 (2) A 24 V AC
Power backup of real-time clock
3 years
Accuracy of real-time clock
±
15 s/year
Содержание ECL 2000
Страница 1: ...Installation Guide ECL 2000 11 99 EI 65 D4 02...
Страница 2: ......
Страница 3: ...Installation Guide ECL 2000 Danfoss A S EI 65 D4 02...
Страница 16: ...Mounting EI 65 D4 02 10...
Страница 26: ...Electrical Connections EI 65 D4 02 20...
Страница 120: ...Application 17 Type 2 Only EI 65 D4 02 114...
Страница 130: ...Appendix C Service Menus EI 65 D4 02 124 C 2 Hot Water Service Menus 0 1 2 3 4 5 1 or or 2 or 3 4 or or...
Страница 131: ...Appendix C Service Menus EI 65 D4 02 125 C 3 Common Function Menus 0 1 2 3 4 5 1 2 etc 3 etc 4 etc...
Страница 132: ...Appendix C Service Menus EI 65 D4 02 126 C 3 Common Function Menus Cont 0 1 2 3 4 5 5 etc 6 7 8 9...
Страница 133: ...Appendix C Service Menus EI 65 D4 02 127 C 3 Common Function Menus Cont 0 1 2 3 4 5 10 11 or or 12 13...
Страница 134: ...Appendix C Service Menus EI 65 D4 02 128...
Страница 136: ...References EI 65 D4 02 130...
Страница 140: ...Index EI 65 D4 02 134...