Electrical Connections
EI.65.D4.02
12
Figure 10. Loop terminals
4.3 Cable Dimensions
The wiring standard outlined in the table below should be observed:
Cable length
Cross section
Cable Screen
Input
Pt 1000
0 – 50 m
50 – 100 m
100 – 200 m
≥
0.4 mm
2
≥
0.75 mm
2
≥
1.5 mm
2
When connecting long cables to
inputs, it is recommended to select
a cable type with screen
0 – 10 V
0.4 – 1.5 mm
2
Pulse
0.4 – 1.5 mm
2
Digital
0.4 – 1.5 mm
2
Output
Relay (pump control)
0.75 – 1.5 mm
2
3-point control (230 V
motor valve control)
0.75 – 1.5 mm
2
3-point control (24 V
motor valve control)
0.4 – 1.5 mm
2
0 – 10 V (24 V motor
valve control)
0.4 – 1.5 mm
2
Note:
When choosing cable type and dimension for installation, local government regu-
lations and applicable international directives must be observed at all times.
Note:
Wire resistance can cause measurement error. For example, a resistance of 4
Ω
corresponds to a measured temperature increase of about 1 degree.
Содержание ECL 2000
Страница 1: ...Installation Guide ECL 2000 11 99 EI 65 D4 02...
Страница 2: ......
Страница 3: ...Installation Guide ECL 2000 Danfoss A S EI 65 D4 02...
Страница 16: ...Mounting EI 65 D4 02 10...
Страница 26: ...Electrical Connections EI 65 D4 02 20...
Страница 120: ...Application 17 Type 2 Only EI 65 D4 02 114...
Страница 130: ...Appendix C Service Menus EI 65 D4 02 124 C 2 Hot Water Service Menus 0 1 2 3 4 5 1 or or 2 or 3 4 or or...
Страница 131: ...Appendix C Service Menus EI 65 D4 02 125 C 3 Common Function Menus 0 1 2 3 4 5 1 2 etc 3 etc 4 etc...
Страница 132: ...Appendix C Service Menus EI 65 D4 02 126 C 3 Common Function Menus Cont 0 1 2 3 4 5 5 etc 6 7 8 9...
Страница 133: ...Appendix C Service Menus EI 65 D4 02 127 C 3 Common Function Menus Cont 0 1 2 3 4 5 10 11 or or 12 13...
Страница 134: ...Appendix C Service Menus EI 65 D4 02 128...
Страница 136: ...References EI 65 D4 02 130...
Страница 140: ...Index EI 65 D4 02 134...