Application 1
EI.65.D4.02
42
System diagram 1B
Heat circuit with direct connection to the district heating network and mixing via
by-pass valve. Hot water tank with continuous control of tank temperature.
Heat circuit
The motor valve M1 controls the flow temperature, which is measured by the sen-
sor S1. The return temperature measured by the sensor S2 can be limited. The cir-
culation pump P1 is running when the reference flow temperature is above 20 °C
or the outdoor temperature is below 2 °C.
Hot-water circuit
The motor valve M2 controls the storage tank temperature, which is measured by
the sensor S4. The return temperature measured by the sensor S5 can be limited.
The circulation pump P2 is controlled according to the 7-day program.
Содержание ECL 2000
Страница 1: ...Installation Guide ECL 2000 11 99 EI 65 D4 02...
Страница 2: ......
Страница 3: ...Installation Guide ECL 2000 Danfoss A S EI 65 D4 02...
Страница 16: ...Mounting EI 65 D4 02 10...
Страница 26: ...Electrical Connections EI 65 D4 02 20...
Страница 120: ...Application 17 Type 2 Only EI 65 D4 02 114...
Страница 130: ...Appendix C Service Menus EI 65 D4 02 124 C 2 Hot Water Service Menus 0 1 2 3 4 5 1 or or 2 or 3 4 or or...
Страница 131: ...Appendix C Service Menus EI 65 D4 02 125 C 3 Common Function Menus 0 1 2 3 4 5 1 2 etc 3 etc 4 etc...
Страница 132: ...Appendix C Service Menus EI 65 D4 02 126 C 3 Common Function Menus Cont 0 1 2 3 4 5 5 etc 6 7 8 9...
Страница 133: ...Appendix C Service Menus EI 65 D4 02 127 C 3 Common Function Menus Cont 0 1 2 3 4 5 10 11 or or 12 13...
Страница 134: ...Appendix C Service Menus EI 65 D4 02 128...
Страница 136: ...References EI 65 D4 02 130...
Страница 140: ...Index EI 65 D4 02 134...