7
Electrical Installation
7.1
Electrical connection
Caution! Electrical installation may only be carried out by an authorized electrician and must follow
applicable local and national regulations.
Caution! The electrical installation must be carried out using permanently routed cables. It must be possible
to isolate the power supply using an all-pole circuit breaker with a minimum contact gap of 3 mm.
DANGER! The terminal blocks are live and can be highly dangerous due to the risk of electric shock. The
power supply must be isolated before electrical installation is started. The heat pump is internally connected
at the factory.
1.
Remove the front cover from the heat pump.
2.
Pull the power supply cable through the opening in the rear of the heat pump to the terminal blocks.
3.
Connect the supply cable to the designated terminal blocks.
See separate manual for wiring diagram.
DANGER! Electrical current! The power cable may only be connected to the terminal block intended for this
purpose. No other terminal blocks may be used!
Electrical cabinet layout
K2
K1
F10
F11
X1
F0 F3 F4
1
E1
1
F1
Figure 14.
Electrical cabinet
Symbol explanation
K1
Contactor compressor
K2
Contactor brine pump
F10
Over current relay compressor.
F11
Over current relay brine pump
F1
Fuse brine pump
F0
Control fuse regulation, overheating
protection compressor
F3
Control fuse heat addition
F4
Control fuse Oil and Electricity
X1
Terminal blocks for incoming supply
and temperature sensor as well as ter-
minal blocks for external components
1
Space for extra board
7.2
Connecting pump hot gas
1.
Connect the hot gas pump to the designated terminal blocks. The voltage is 230 VAC. The pump is designed
to be placed outside the heat pump casing and must be connected with flexible hoses.
This pump runs in parallel with the compressor.
See separate manual wiring diagram.