Adaptation to the heating system
Adjust the heat pump settings to the applicable heating system, for instance an underfloor heating or radiator system.
The delta temperature must be at least 8°C above the heat pump. The delta temperature should be 3–5°C for the
brine system. If none of the delta temperatures are reached, the flow of the circulation pumps may need adjusting
depending on the applicable heating system.
9.1.1
Noise check
During transportation and installation there is a certain risk that the heat pump can be damaged, components may
move or get bent and this can cause noise. Because of this it is important to check the heat pump when it has been
installed and is ready to be commissioned to ensure that everything is in order. The heat pump should be tested in
both heating and hot water modes to ensure that there is no abnormal noise. While doing this, check that there is
no abnormal noise in other parts of the house.
9.1.2
Select operating mode
Set the heat pump to the desired operating mode in the menu INFORMATION -> OPERAT. If necessary, set certain
parameters in the control system, such as ROOM and CURVE.
Installation instructions
VMIFJ102
– 25