40 – Service
VMBMH302
Menu selection
Meaning
Factory setting
VERSION
Shows the software version which is stored on the display card
respectively the I/O-card.
DISPLAY: V n.n
I/O-CARD: V n.n
-
LOG TIME
Time interval between collection points of temperature history
in minutes. The history graphs always show the 60 last collection
points, which means that the graphs can display history from 1
hour up to 60 hours ago.
(The function is not active if there is an active alarm).
1M (interval: 1M / 60M)
TOPH. TIME
= Deactivates time period for peak heat charging.
ON = Activates time period for peak heat charging.
13.2.6 Sub menu SERVICE -> DEFROST
Used to change settings for heat pump defrost.
Menu selection
Meaning
Factory setting
DEFR CURVE 0
The temperature of the heat pump’s incoming refrigerant at
which defrosting should start, at 0°C outdoor temperature is set
here, using + or -.
The graph can be changed up or down at 0°C outdoor tempe-
rature in the display. See section
11.5 Important parameters
for
further information.
-10°C
(interval: -16°C / 0°C)
DEFR CURVE -XX
The temperature of the heat pump’s incoming refrigerant at
which defrosting should start, at the set outdoor temperature for
OUTDOOR STOP is set here, using + or -.
The setting is made by reducing the OUTDOOR STOP value by
this value.
The number of degrees shown after DEFR CURVE in the display is
the set value for OUTDOOR STOP. The combined temperature is
shown in the top right corner of the display.
The graph can be changed up or down at the outdoor tempera-
ture OUTDOOR STOP in the display. See section
11.5 Important
parameters
for further information.
OUTDOOR STOP reduced
by 4°C
(interval: -5°C / -1°C)
STOP DEFR
The temperature that must be reached on incoming refrigerant
to complete a defrost.
30°C (interval: 7°C / 60°C)
BELOW 5°C DEFR
Safety defrosting occurs when the outdoor temperature has
been below 5° for a set number of days.
7D
(interval: , 1D / 14D)
MIN TIME DEFR
Minimum time between two defrosts in minutes.
45M
(interval: 10M / 60M)
MIN RAD STMP
Minimum permitted supply temperature during defrost, at
which the electric auxiliary heater engages.
20°C
(interval: 16°C / 30°C)
FAN START
The fan starts when the temperature of the incoming refrigerant
to the heat pump reaches the set value.
If FAN START is set to ON, the fans starts and stops at the same
time as the compressor and the FAN STOP parameter is inactive.
-2°C
(interval: ON, -5°C / FAN
STOP-3°C)
FAN STOP
The fan stops when the temperature of the incoming refrigerant
to the heat pump reaches the set value.
17°C
(interval: FAN START+3°C
/ 30°C)
REFR 3
Shows the temperature at refrigerant sensor 3.
Содержание DHP-AX
Страница 1: ...VMBMH302 Danfoss DHP AX Installation and Service instructions ...
Страница 7: ...Service 7 VMBMH302 Installation instructions ...
Страница 20: ...20 Service VMBMH302 Service instructions ...
Страница 41: ...Service 41 VMBMH302 ...
Страница 68: ...68 Service VMBMH302 ...
Страница 69: ...Service 69 VMBMH302 ...
Страница 70: ...VMBMH302 ...