34 – Service
VMBMH302
Menu selection
Meaning
Factory setting
POOL
(Expansion card)
Only appears if POOL is selected. The temperature in the pool
is controlled by a separate sensor regardless of the heating and
hot water system.
20°C
(interval: , 5°C / 40°C)
POOL HYSTERESIS
(Expansion card)
Only appears if POOL is selected. In simple terms, the POOL
HYSTERESIS is the temperature interval between start and stop
for pool heating. If the difference between the actual supply
temperature to pool and the calculated supply temperature is
too great, either the integral value is set to start value A1 (the
heat pump starts) or the value is set to 0 (stops the heat pump).
2°C (interval: 1°C / 10°C)
13.1.3 Sub menu INFORMATION -> HEAT CURVE 2
Only appears if shunt group sensor (T2) is connected and activated in menu SERVICE -> INSTALLATION ->
SYSTEM -> SHUNT GROUP. Used to change settings for heat curve 2.
Menu selection
Meaning
Factory setting
CURVE 2
Calculated shunt group temperature at 0°C outdoor tempera-
ture. Shown as a graph that also shows MIN and MAX values.
40°C
(interval: 22°C / 56°C)
MIN
Minimum permitted shunt group temperature, if the tempera-
ture for heat stop has not been reached.
10°C
(interval: 10°C / 50°C)
MAX
Maximum permitted shunt group temperature.
55°C
(interval: 15°C / 70°C)
13.1.4 Sub menu INFORMATION -> TEMPERATURE
Used to indicate the prevailing temperatures, history and set/calculated values. History can be accessed to
view all the values by pressing the right arrow to present a graph of the last 60 measurement points for the set
time interval (SERVICE -> INSTALLATION -> LOGTIME). In the event of an alarm, history stops being logged until
the alarm is reset by changing the operating mode to OFF.
Menu selection
Meaning
Factory setting
OUTD
Shows the actual outdoor temperature.
-
ROOM
Shows the actual set temperature.
-
SUPPLY LINE
Shows the actual supply temperature. The calculated supply
temperature to the heating system group is within brackets.
During hot water production in operating mode AUX. HEATER
the value for HOT WATER STOPP + 5° is shown within brackets.
-
RETURN LINE
Shows the actual return temperature. The stop temperature,
MAX RETURN is within brackets.
-
HOT WATER
Shows the actual hot water temperature.
-
INTEGRAL
Shows the actual calculated value for integral.
-
REFR 1
Shows the actual temperature of the refrigerant.
-
REFR 2
Shows the actual temperature of the refrigerant.
-
POOL
(Expansion card)
Only appears if POOL is selected. Shows the actual pool tempe-
rature. The set pool temperature is shown in brackets.
-
SHUNT GROUP
Only appears if SHUNT GROUP is selected. Shows the actual
supply temperature. The calculated supply temperature to the
shunt group is within brackets.
-
CURRENT
(Expansion card)
Only appears if CURRENT LIMITER is selected. Shows the actual
current consumption. The set value for MAX CURRENT is shown
between brackets.
-
Содержание DHP-AX
Страница 1: ...VMBMH302 Danfoss DHP AX Installation and Service instructions ...
Страница 7: ...Service 7 VMBMH302 Installation instructions ...
Страница 20: ...20 Service VMBMH302 Service instructions ...
Страница 41: ...Service 41 VMBMH302 ...
Страница 68: ...68 Service VMBMH302 ...
Страница 69: ...Service 69 VMBMH302 ...
Страница 70: ...VMBMH302 ...