![background image](http://html1.mh-extra.com/html/danfoss/c67/c67_user-manual_3510461061.webp)
The grey
side of the
ECL Card
Ex
tended ser
vic
e
32o
Service parameter(s) 67-78
67 Adaptive function of S2 flow temperature during
DHW charging
Circuit
Setting range
Factory setting
I
OFF / 1 ... 50
20
This setting is only used for system types 10.5 and 10.5a.
The setting will eliminate the difference between the desired and
actual S5 charging temperature by integrating the difference and
adjusting the desired S2 flow temperature.
OFF:
The desired flow temperature will not be
adjusted any further.
1:
The desired flow temperature will be
adjusted quickly.
50:
The desired flow temperature will be
adjusted slowly.
78 Desired temperature for anti-bacteria function
Circuit
Setting range
Factory setting
I
OFF / 1 ... 100 °C
OFF
Set the desired temperature for the anti-bacteria function. The
DHW will be charged once a day (from 00:00) or once a week
(Mondays from 00:00) at the set temperature to protect against
bacteria.
The selection of the daily / weekly anti-bacteria function is set in
line 83. The DHW is charged according to the period set in line 80.
OFF:
The anti-bacteria function is not active.
1 ... 100:
The anti-bacteria function is active at the
desired temperature.