Service parameter(s) 196-198
196 Service pin - LON
Circuit
Setting range
Factory setting
I
ON / OFF
OFF
This setting is only used in connection with LON communication
(see the documentation for the used communication unit).
197 LON reset
Circuit
Setting range
Factory setting
I
ON / OFF
ON
This setting is only used in connection with LON communication
(see the documentation for the used communication unit).
198 Daylight saving time changeover
Circuit
Setting range
Factory setting
I
ON / OFF
ON
Choose whether you want the change to summer / winter time to
be automatic or manual.
ON:
The controller’s built-in clock automatically
c / - one hour on the standardized
days for daylight saving time changeover
for Central Europe.
OFF:
You change manually between summer and
winter time by setting the clock backward
or forward.