Con
tr
ol & o
ver
vie
w
s
31b
Service parameters (10-199)
Circuit I (Heating and DHW)
Lines Setting ranges
Factory settings Your settings
43
Parallel operation of DHW and heating
circuits
OFF / 1 ... 99 K
OFF
K
44
Max. DHW charging time
0 ... 250 min.
0 min.
min.
45
DHW charging deactivation time
0 ... 250 min.
0 min.
min.
51
DHW charging pump / changeover
valve
ON / OFF
OFF
53
Desired flow temperature, DHW
charging
ON / OFF
OFF
55
Activation / deactivation of DHW
circulation during DHW charging
ON / OFF
OFF
67
Adaptive function of S2 flow
temperature during DHW charging
OFF / 1 ... 50
20
78
Desired temperature for anti-bacteria
function
OFF / 1 ... 100 °C
OFF
°C
80
Anti-bacteria function period
5 ... 250 min.
120 min.
min.
83
Daily / weekly anti-bacteria function
ON / OFF
ON
140
Function of temperature sensor S5
0, 1, 2
0
141
Override input selection
OFF / 1 ... 6
OFF
152
Max. limitation temperature at S2
during DHW charging
10 ... 110 °C
110 °C
°C
174
Motor protection
OFF / 10 ... 59 min.
OFF
min.
194
Temperature difference at DHW
charging, cut-out temperature
difference - lower tank temperature
sensor
1 ... 30 K
15 K
K
195
Temperature difference at DHW
charging, cut-in temperature
difference - upper tank temperature
sensor
1 ... 30 K
20 K
K
196
Service pin LON
ON / OFF
OFF
197
LON reset
ON / OFF
ON
198
Daylight saving time changeover
ON / OFF
ON
199
Slave address
0 ... 9, 15
15
Содержание C67
Страница 4: ......
Страница 15: ...Installation 11b...
Страница 23: ...Installation...
Страница 45: ...Control overviews...