Danfoss BW10 020-090 Скачать руководство пользователя страница 36

36

14 - MAINTENANCE

During the unit operating life the service checks and tests must 

be carried out in accordance with applicable national 

regulations.

If there are no similar criteria in local regulations, the 

information on checks during operation in annex C of standard 

EN 378-2 can be used.

External visual checks: annex A and B of standard EN378-2.

Corrosion checks: annex D of standard EN 378-2. These 

controls must be carried out:

• 

After an intervention that is likely to affect the resis-tance 

or a change in use or change of high-pressure refrigerant, 

or after a shut down of more than two years. Components 

that do not comply, must be changed. Test pressures above 

the respective component design pressure must not be 

applied (annex B and D).

• 

After repair or significant modifications or significant 

system or component extension (annex B).

• 

After re-installation at another site (annexes A, B and D).

• 

After repair following a refrigerant leak (annex D). The 

frequency of refrigerant leak detection can vary from once 

per year for systems with less than 1% leak rate per year 

to once a day for systems with a leak rate of 35% per year 

or more. The frequency is in proportion with the leak rate.

NOTE: High leak rates are not acceptable. The necessary 

steps must be taken to eliminate any leak detected.

NOTE 2: Fixed refrigerant detectors are not leak detectors, as 

they cannot locate the leak.

14.1 - Soldering and welding

Component, piping and connection soldering and welding 

operations must be carried out using the correct procedures and 

by qualified operators. Pressurised containers must not be 

subjected to shocks, nor to large temperature variations during 

maintenance and repair operations. 

Any technician attending the machine for any purpose must be 

fully qualified to work on refrigerant and electrical circuits.

WARNING: Before doing any work on the machine ensure 

that the power is switched off. If a refrigerant circuit is 

opened, it must be evacuated, recharged and tested for leaks. 

Before any operation on a refrigerant circuit, it is necessary 

to remove the complete refrigerant charge from the unit with 

a refrigerant charge recovery unit.

All removal and refrigerant draining operations must be 

carried out by a qualified technician and with the correct 

material for the unit. Any inappropriate handling can lead to 

uncontrolled fluid or pressure leaks.

If an oil draining or recovery operation becomes necessary, the 

fluid transfer must be made using mobile containers.

14.2 - General unit maintenance

• 

Keep the unit itself and the space around it clean and free 

of obstructions. Remove all rubbish such as packing 

materials, as soon as the installation is completed.

• 

Regularly clean the exposed pipework to remove all dust 

and dirt. This makes detection of water leaks easier, and 

they can be repaired before more serious faults develop.

• 

Confirm that all screwed and bolted connections and joints 

are secure.

• 

Secure connections prevent leaks and vibration from 

developing. 

• 

Check that all foam insulation joints on the heat exchanger 

piping are in good condition. 

14.3 - Refrigerant undercharge

If there is not enough refrigerant in the system, this is indicated 

by gas bubbles in the moisture sight glass.

If the undercharge is significant, large bubbles appear in the 

moisture sight glass, and the suction pressure drops. The 

compressor suction superheat is also high. The machine must be 

recharged after the leak has been repaired.

Find the leak and completely drain the system with a 

refrigerant recovery unit. Carry out the repair, leak test and 

then recharge the system.

IMPORTANT: After the leak has been repaired, the circuit 

must be tested, without exceeding the maximum low-side 

operating pressure shown on the unit name plate.

The refrigerant must always be recharged in the liquid phase into 

the liquid line. The refrigerant cylinder must always contain at 

least 10% of its initial charge. For the refrigerant quantity per 

circuit, refer to the data on the unit name plate.

During applications with option 272 (brine to water) and with 

positive evaporation, bubbles will appear in the sight-glass. 

This is normal, when the charge is optimised for improved 

efficiency in brine applications.

14.4 - Refrigerant guidelines 

Refrigeration installations must be inspected and maintained 

regularly and rigorously by specialists. Their activities must be 

overseen and checked by properly trained people. To minimise 

discharge to the atmosphere, refrigerants and lubricating oil 

must be transferred using methods which reduce leaks and 

losses to a minimum.

• 

Leaks must be repaired immediately.

• 

If the residual pressure is too low to make the transfer 

alone, a purpose-built refrigerant recovery unit must be 

used.

• 

Compressor lubricating oil contains refrigerant. Any oil 

drained from a system during maintenance must therefore 

be handled and stored accordingly.

• 

Refrigerant under pressure must never be discharged to 

the atmosphere.

Содержание BW10 020-090

Страница 1: ...20 090 Water Sourced Heat Pumps with or without Integrated Hydronic Modules Nominal cooling capacity 24 95 kW Nominal heating capacity 30 116 kW Installation operation and maintenance instructions VMG...

Страница 2: ...options 116 274 270 274 116 270 274 14 3 14 BW10 050 090 stackable unit option 273 14 4 PHYSICAL AND ELECTRICAL DATA BW10 15 4 1 Physical data BW10 15 4 3 Physical data BW10 units with hydronic module...

Страница 3: ...33 12 6 High pressure switch and high pressure sensor 33 12 7 High and low pressure side safety valves 33 12 8 Moisture indicator 33 12 9 Filter drier in the refrigerant circuit 34 12 10 Fixed speed...

Страница 4: ...de of plastic and should not be used If they are still present please remove them Install devices at the valve outlets or drain piping that prevent the penetration of foreign bodies dust building debr...

Страница 5: ...lete removal of the refrigerant charge For these units transfer of the refrigerant charge from the high or low pressure side is not possible nor permitted During any handling maintenance and service o...

Страница 6: ...ills from the skin with soap and water If liquid refrigerant enters the eyes immediately and abundantly flush the eyes with water and consult a doctor Never apply an open flame or live steam to a refr...

Страница 7: ...See chapter 1 1 Installation safety considerations 2 2 2 Siting the unit Always refer to the chapter Dimensions and clearances to confirm that there is adequate space for all connections and service...

Страница 8: ...rify that all documents for pressure containers certifi cates name plates files instruction manuals provided by the manufacturer to comply with the regulations are present Verify the free passage of a...

Страница 9: ...er outlet Power wiring connection 161 237 153 470 160 237 153 470 1058 900 700 700 1044 600 625 901 700 2 2 1 1 4 4 4 4 5 3 3 3 2 BW10 020 045 unit with top connections option 274 901 938 86 105 104 1...

Страница 10: ...1044 1058 1463 704 600 625 700 379 4 4 4 4 5 2 2 1 1 3 3 398 153 161 623 1021 142 237 2 2 1 1 398 153 470 398 161 142 623 2 2 1 1 Legend All dimensions are in mm Evaporator Condenser Safety valve Cle...

Страница 11: ...The water and electrical connections are identical to those of the standard unit 1014 1014 1058 600 1841 900 700 700 700 4 4 4 4 Legend All dimensions are in mm Evaporator Condenser Safety valve Clea...

Страница 12: ...0 900 700 253 142 168 142 80 1474 901 938 880 700 700 2 1 4 4 4 4 4 Legend All dimensions are in mm Evaporator Condenser Safety valve Clearances required for maintenance see note Control box Water inl...

Страница 13: ...0 unit with condenser hydronic module option 270 3 12 BW10 050 090 unit with evaporator condenser hydronic modules options 116 270 Legend All dimensions are in mm Evaporator Condenser Safety valve Cle...

Страница 14: ...14 BW10 050 090 stackable unit option 273 NOTE The water and electrical connections are identical to those of the standard unit Legend All dimensions are in mm Evaporator Condenser Safety valve Clear...

Страница 15: ...option 272 kg 2 7 2 8 2 8 2 9 2 9 3 9 7 2 7 6 7 9 8 4 10 5 Oil 160SZ Charge per compressor l 3 3 3 3 3 3 3 3 3 3 6 3 3 3 3 3 3 3 3 3 6 Evaporator Direct expansion plate heat exchanger Water volume l 3...

Страница 16: ...wer input and 360 V 4 5 Short circuit stability current TN system standard unit with main disconnect switch BW10 020 025 030 035 040 045 050 060 070 080 090 Value without upstream protection Short ter...

Страница 17: ...ps 20 25 30 35 40 45 50 60 70 80 90 1 Nominal efficiency at full load and nominal voltage 82 82 82 82 82 82 82 82 82 82 82 1 Nominal efficiency at 75 rated load and nominal voltage 82 82 82 82 82 82 8...

Страница 18: ...unit 5 The factory installed disconnect switch es circuit breaker s is are of a type suitable for power interruption in accordance with EN 60947 6 The units are designed for simplified connection on...

Страница 19: ...10 K unit without hydronic module Maximum flow rate for an available pressure of 20 kPa unit with low pressure hydronic module or 50 kPa unit with high pressure hydronic module Maximum flow rate for a...

Страница 20: ...ethylene glycol l 100 70 35 150 100 50 35 ethylene glycol l 85 55 30 130 85 45 5 10 Expansion tank The expansion tank is supplied with a pressure of 1 bar relative 20 The maximum operating pressure f...

Страница 21: ...6 7 8 9 10 11 12 13 5 12 Plate heat exchanger pressure drop includes internal piping Evaporator standard unit without hydronic module BW10 020 045 BW10 050 090 1 BW10 020 2 BW10 025 to BW10 030 3 BW10...

Страница 22: ...e 100 x max deviation from average voltage Average voltage Example On a 400 V 3 ph 50 Hz supply the individual phase voltages were measured to be AB 406 V BC 399 AC 394 V Average voltage 406 399 394 3...

Страница 23: ...imensional drawings supplied with the unit The water pipes must not transmit any radial or axial force to the heat exchangers nor any vibration The water supply must be analysed and appropriate filter...

Страница 24: ...e Do not introduce any significant static or dynamic pressure into the heat exchange circuit with regard to the design operating pressures Before any start up verify that the heat exchange fluid is co...

Страница 25: ...to ensure correct flow control With the pressure loss generated by the control valve in the hydronic system the valve is able to impose the system pressure flow curve on the pump pressure flow curve...

Страница 26: ...rence Entering water pressure reading Leaving water pressure reading O F F O F F Example Unit with a given nominal flow rate of 4 8 l s Water flow rate l s Legend 1 Unit pump curve 2 Plate heat exchan...

Страница 27: ...8 9 50 60 70 80 90 100 110 120 130 140 150 160 0 0 0 5 1 0 1 5 2 0 2 5 3 0 3 5 4 0 4 5 50 70 90 110 130 150 170 190 210 0 1 2 3 4 5 6 7 8 Condenser 9 2 Available static system pressure fixed or varia...

Страница 28: ...iable speed low pressure pumps units with hydronic module Evaporator 1 BW10 020 2 BW10 025 to BW10 030 3 BW10 035 4 BW10 040 5 BW10 045 6 BW10 050 7 BW10 060 8 BW10 070 9 BW10 080 10 BW10 090 1 BW10 0...

Страница 29: ...e speed pump High pressure pumps BW10 options 116J 270J Pressure head kPa Water flow rate l s 1 BW10 020 050 2 BW10 060 080 3 BW10 090 0 20 40 60 80 100 120 140 160 180 200 220 0 1 2 3 4 5 6 7 8 9 10...

Страница 30: ...30...

Страница 31: ...a condensate pan must be added under the unit that collects 100 of the condensate If work is required in a control box or on the compressor wiring the phase order must be verified with a quick test r...

Страница 32: ...lubricant shown on the compressor name plate polyolester oil ref POE 160SZ 12 3 Evaporators and condensers The evaporators and condensers are single circuit plate heat exchangers They are tested and s...

Страница 33: ...rbidden Only the replacement of the complete heat exchanger by an original heat exchanger supplied by the manufacturer is permitted The replacement must be carried out by a qualified technician The he...

Страница 34: ...essure curve The system flow rate is automatically adjusted via the frequency converter built into the pump based on the heat rejection load on the drycooler The maximum permitted concentration of the...

Страница 35: ...o be installed on the drycooler for communication with the unit via a bus Permits the use of an energy efficient plug and play system Control of multi source heating system 157 Additional control box...

Страница 36: ...If an oil draining or recovery operation becomes necessary the fluid transfer must be made using mobile containers 14 2 General unit maintenance Keep the unit itself and the space around it clean and...

Страница 37: ...stress on the compressor motor when the system has been evacuated There is a risk of internal short circuits between the motor windings Do not use additives for leak detection Do not use CFCs HCFCs a...

Страница 38: ...sor problems The following periodic preventive maintenance checks are strongly recommended Check the operating conditions evaporating tempera ture condensing temperature discharge temperature heat exc...

Страница 39: ...rs disconnect switch and transformer Check the phase direction upstream of the unit and in the customer s electrical data table Check the status of the contactors and fuses Carry out a quick test refe...

Страница 40: ...re has been connected Electrical circuit protection has been sized and installed properly All terminals are tight All cables and thermistors have been inspected for crossed wires All plug assemblies a...

Страница 41: ...reater than unit s minimum flow rate Total l s meets job specified requirement of l s Perform TEST function indicate positive result WARNING Once power is supplied to the unit check the display for an...

Страница 42: ...VMGFT102...

Отзывы: