4.7 - Compressor usage and electrical data table

Compressor

Reference

I Nom I Max

(Un)

I Max
(Un - 10%)

LRA* LRA** Circ. BW10

020

025

030

040

045

060

070

080

090

110

120

SH090

00PSG001549100

10.5

16.1

19

98

53.9

A

1

SH105

00PSG001549200

13.2

19.6

22

142

78.1

A

1

2

SH120

00PSG001549300

13.8

21.1

24

142

78.1

A

1

2

SH140

00PSG001549400

15.6

24.4

28

147

80.9

A

1

2

SH161

00PSG001549500

16.2

26.7

31

158

86.9

A

1

2

SH184

00PSG001549600

20.2

30.9

36

197

108.4

A

1

2

Legend

I Nom  Nominal current draw (A) at standard Eurovent conditions see definition of conditions under nominal unit current draw)
I Max  Maximum operating current, A
LRA*  Locked rotor current at nominal voltage, A
LRA**  Locked rotor current with electronic starter at nominal voltage, A

 

 

 

 

 

Electrical data notes and operating conditions:

• 

BW10 units have a single power connection point, located immediately upstream 

of the main disconnect switch.

• 

The control box includes the following standard features:

 

- a main disconnect switch, 

 

- the starter and motor protection devices for each compressor and the pumps

 

- the control devices

• 

Field connections:

 

All connections to the system and the electrical installations must be in full 
accordance with all applicable local codes.

• 

The BW10 units are designed and built to ensure conformance with these codes. 

The recommendations of European standard EN 60204-1 (machine safety - 
electrical machine components - part 1: general regulations - corresponds to IEC 
60204-1) are specifically taken into account, when designing the electrical unit 
equipment.

NOTES:

• 

Generally the recommendations of IEC 60364 are accepted as compliance with the 

requirements of the installation directives. Conformance with EN 60204-1 is the 
best means of ensuring compliance with the Machines Directive § 1.5.1. 

• 

Annex B of EN 60204-1 describes the electrical characteristics used for the 

operation of the machines.

1.  The operating conditions for the units are specified below:
 

Environment* - Environment as classified in IEC 60364 § 3:

 

-  ambient temperature range: +5°C to +40°C, class AA4

 

-  humidity range (non-condensing)*:

 

  - 50% relative humidity at 40°C

 

  - 90% relative humidity at 20°C

 

-  altitude: ≤ 2000 m (see note for table 4.6 - Electrical data, hydronic module)

 

-  indoor installation*

 

-  presence of water: class AD2 (possibility of water droplets)

 

-  presence of hard solids, class 4S2 (no significant dust present)

 

-  presence of corrosive and polluting substances, class 4C2 (negligible)

 

-  vibration and shock, class AG2, AH2

 

-  competence of personnel, class BA4* (trained personnel - IEC 60364)

2.  Power supply frequency variation: ± 2 Hz.
3.  The neutral (N) conductor must not be connected directly to the unit (if necessary 

use a transformer).

4.  Over-current protection of the power supply conductors is not provided with the 

unit.

5.  The factory-installed disconnect switch(es)/circuit breaker(s) is (are) of a type 

suitable for power interruption in accordance with EN 60947.

6.  The units are designed for simplified connection on TN(s) networks (IEC 60364). 

For IT networks provide a local earth and consult competent local organisations to 
complete the electrical installation.

7.  Derived currents: If protection by monitoring of derived currents is necessary to 

ensure the safety of the installation, the control of the cut-out value must take the 
presence of leak currents into consideration that result from the use of frequency 
converters in the unit. A value of at least 150 mA is recommended to control 
differential protection devices.

NOTE: If particular aspects of an actual installation do not conform to the 
conditions described above, or if there are other conditions which should be 
considered, always contact your local  Danfoss representative.

The protection level of the control boxes required to conform to this class is IPX1B 
(according to reference document IEC 60529). All BW10 units fulfil this protection 
condition.

 

Units equipped with front casing panel meet class IP23. If the casing panel has 
been removed, access to energised components is protected to level IPXXB.

5 - APPLICATION DATA

5.1 - Operating limits

BW10

Minimum

Maximum

Evaporator

Entering water temperature at start-up

°C

7.5*

27

Leaving water temperature during operation

°C

5**

20

Entering/leaving water temperature difference

K

2.5

7

Condenser

Entering water temperature at start-up

°C

15***

60****

Leaving water temperature during operation

°C

20

65

Entering/leaving water temperature difference

K

2.5

18

For entering water temperatures below 7.5°C at start-up, contact  Danfoss.

**  If the leaving water temperature is below 5°C, a frost protection solution must 

be used. Please refer to option 6 for evaporator leaving water low-temperature 
applications (< 5°C).

***  For applications with a condenser entering air temperature below 15°C the use of 

a three-way valve is recommended. This three-way valve can be controlled by the 
0-10 V analogue output of the control system.

****  For a water flow rate that corresponds to a maximum water-side temperature 

difference of 5 K.

BW10 + option 272 (geothermal application)

Minimum

Maximum

Evaporator

Entering water temperature at start-up

°C

-2.5*

25

Leaving water temperature during operation

°C

-5*

20

Entering/leaving water temperature difference

K

2.5

5

Condenser

Entering water temperature at start-up

°C

15**

60***

Leaving water temperature during operation

°C

20

65

Entering/leaving water temperature difference

K

2.5

18

A frost protection solution must be used.

**  For applications with a condenser entering air temperature below 15°C the use of 

a three-way valve is recommended. This three-way valve can be controlled by the 
0-10 V analogue output of the  control system.

***  For a water flow rate that corresponds to a maximum water-side temperature 

difference of 5 K.

Содержание BW10 020-090

Страница 1: ...20 090 Water Sourced Heat Pumps with or without Integrated Hydronic Modules Nominal cooling capacity 24 95 kW Nominal heating capacity 30 116 kW Installation operation and maintenance instructions VMG...

Страница 2: ...options 116 274 270 274 116 270 274 14 3 14 BW10 050 090 stackable unit option 273 14 4 PHYSICAL AND ELECTRICAL DATA BW10 15 4 1 Physical data BW10 15 4 3 Physical data BW10 units with hydronic module...

Страница 3: ...33 12 6 High pressure switch and high pressure sensor 33 12 7 High and low pressure side safety valves 33 12 8 Moisture indicator 33 12 9 Filter drier in the refrigerant circuit 34 12 10 Fixed speed...

Страница 4: ...de of plastic and should not be used If they are still present please remove them Install devices at the valve outlets or drain piping that prevent the penetration of foreign bodies dust building debr...

Страница 5: ...lete removal of the refrigerant charge For these units transfer of the refrigerant charge from the high or low pressure side is not possible nor permitted During any handling maintenance and service o...

Страница 6: ...ills from the skin with soap and water If liquid refrigerant enters the eyes immediately and abundantly flush the eyes with water and consult a doctor Never apply an open flame or live steam to a refr...

Страница 7: ...See chapter 1 1 Installation safety considerations 2 2 2 Siting the unit Always refer to the chapter Dimensions and clearances to confirm that there is adequate space for all connections and service...

Страница 8: ...rify that all documents for pressure containers certifi cates name plates files instruction manuals provided by the manufacturer to comply with the regulations are present Verify the free passage of a...

Страница 9: ...er outlet Power wiring connection 161 237 153 470 160 237 153 470 1058 900 700 700 1044 600 625 901 700 2 2 1 1 4 4 4 4 5 3 3 3 2 BW10 020 045 unit with top connections option 274 901 938 86 105 104 1...

Страница 10: ...1044 1058 1463 704 600 625 700 379 4 4 4 4 5 2 2 1 1 3 3 398 153 161 623 1021 142 237 2 2 1 1 398 153 470 398 161 142 623 2 2 1 1 Legend All dimensions are in mm Evaporator Condenser Safety valve Cle...

Страница 11: ...The water and electrical connections are identical to those of the standard unit 1014 1014 1058 600 1841 900 700 700 700 4 4 4 4 Legend All dimensions are in mm Evaporator Condenser Safety valve Clea...

Страница 12: ...0 900 700 253 142 168 142 80 1474 901 938 880 700 700 2 1 4 4 4 4 4 Legend All dimensions are in mm Evaporator Condenser Safety valve Clearances required for maintenance see note Control box Water inl...

Страница 13: ...0 unit with condenser hydronic module option 270 3 12 BW10 050 090 unit with evaporator condenser hydronic modules options 116 270 Legend All dimensions are in mm Evaporator Condenser Safety valve Cle...

Страница 14: ...14 BW10 050 090 stackable unit option 273 NOTE The water and electrical connections are identical to those of the standard unit Legend All dimensions are in mm Evaporator Condenser Safety valve Clear...

Страница 15: ...option 272 kg 2 7 2 8 2 8 2 9 2 9 3 9 7 2 7 6 7 9 8 4 10 5 Oil 160SZ Charge per compressor l 3 3 3 3 3 3 3 3 3 3 6 3 3 3 3 3 3 3 3 3 6 Evaporator Direct expansion plate heat exchanger Water volume l 3...

Страница 16: ...wer input and 360 V 4 5 Short circuit stability current TN system standard unit with main disconnect switch BW10 020 025 030 035 040 045 050 060 070 080 090 Value without upstream protection Short ter...

Страница 17: ...ps 20 25 30 35 40 45 50 60 70 80 90 1 Nominal efficiency at full load and nominal voltage 82 82 82 82 82 82 82 82 82 82 82 1 Nominal efficiency at 75 rated load and nominal voltage 82 82 82 82 82 82 8...

Страница 18: ...unit 5 The factory installed disconnect switch es circuit breaker s is are of a type suitable for power interruption in accordance with EN 60947 6 The units are designed for simplified connection on...

Страница 19: ...10 K unit without hydronic module Maximum flow rate for an available pressure of 20 kPa unit with low pressure hydronic module or 50 kPa unit with high pressure hydronic module Maximum flow rate for a...

Страница 20: ...ethylene glycol l 100 70 35 150 100 50 35 ethylene glycol l 85 55 30 130 85 45 5 10 Expansion tank The expansion tank is supplied with a pressure of 1 bar relative 20 The maximum operating pressure f...

Страница 21: ...6 7 8 9 10 11 12 13 5 12 Plate heat exchanger pressure drop includes internal piping Evaporator standard unit without hydronic module BW10 020 045 BW10 050 090 1 BW10 020 2 BW10 025 to BW10 030 3 BW10...

Страница 22: ...e 100 x max deviation from average voltage Average voltage Example On a 400 V 3 ph 50 Hz supply the individual phase voltages were measured to be AB 406 V BC 399 AC 394 V Average voltage 406 399 394 3...

Страница 23: ...imensional drawings supplied with the unit The water pipes must not transmit any radial or axial force to the heat exchangers nor any vibration The water supply must be analysed and appropriate filter...

Страница 24: ...e Do not introduce any significant static or dynamic pressure into the heat exchange circuit with regard to the design operating pressures Before any start up verify that the heat exchange fluid is co...

Страница 25: ...to ensure correct flow control With the pressure loss generated by the control valve in the hydronic system the valve is able to impose the system pressure flow curve on the pump pressure flow curve...

Страница 26: ...rence Entering water pressure reading Leaving water pressure reading O F F O F F Example Unit with a given nominal flow rate of 4 8 l s Water flow rate l s Legend 1 Unit pump curve 2 Plate heat exchan...

Страница 27: ...8 9 50 60 70 80 90 100 110 120 130 140 150 160 0 0 0 5 1 0 1 5 2 0 2 5 3 0 3 5 4 0 4 5 50 70 90 110 130 150 170 190 210 0 1 2 3 4 5 6 7 8 Condenser 9 2 Available static system pressure fixed or varia...

Страница 28: ...iable speed low pressure pumps units with hydronic module Evaporator 1 BW10 020 2 BW10 025 to BW10 030 3 BW10 035 4 BW10 040 5 BW10 045 6 BW10 050 7 BW10 060 8 BW10 070 9 BW10 080 10 BW10 090 1 BW10 0...

Страница 29: ...e speed pump High pressure pumps BW10 options 116J 270J Pressure head kPa Water flow rate l s 1 BW10 020 050 2 BW10 060 080 3 BW10 090 0 20 40 60 80 100 120 140 160 180 200 220 0 1 2 3 4 5 6 7 8 9 10...

Страница 30: ...30...

Страница 31: ...a condensate pan must be added under the unit that collects 100 of the condensate If work is required in a control box or on the compressor wiring the phase order must be verified with a quick test r...

Страница 32: ...lubricant shown on the compressor name plate polyolester oil ref POE 160SZ 12 3 Evaporators and condensers The evaporators and condensers are single circuit plate heat exchangers They are tested and s...

Страница 33: ...rbidden Only the replacement of the complete heat exchanger by an original heat exchanger supplied by the manufacturer is permitted The replacement must be carried out by a qualified technician The he...

Страница 34: ...essure curve The system flow rate is automatically adjusted via the frequency converter built into the pump based on the heat rejection load on the drycooler The maximum permitted concentration of the...

Страница 35: ...o be installed on the drycooler for communication with the unit via a bus Permits the use of an energy efficient plug and play system Control of multi source heating system 157 Additional control box...

Страница 36: ...If an oil draining or recovery operation becomes necessary the fluid transfer must be made using mobile containers 14 2 General unit maintenance Keep the unit itself and the space around it clean and...

Страница 37: ...stress on the compressor motor when the system has been evacuated There is a risk of internal short circuits between the motor windings Do not use additives for leak detection Do not use CFCs HCFCs a...

Страница 38: ...sor problems The following periodic preventive maintenance checks are strongly recommended Check the operating conditions evaporating tempera ture condensing temperature discharge temperature heat exc...

Страница 39: ...rs disconnect switch and transformer Check the phase direction upstream of the unit and in the customer s electrical data table Check the status of the contactors and fuses Carry out a quick test refe...

Страница 40: ...re has been connected Electrical circuit protection has been sized and installed properly All terminals are tight All cables and thermistors have been inspected for crossed wires All plug assemblies a...

Страница 41: ...reater than unit s minimum flow rate Total l s meets job specified requirement of l s Perform TEST function indicate positive result WARNING Once power is supplied to the unit check the display for an...

Страница 42: ...VMGFT102...

Отзывы: