17
4.6 - Electrical data, optional hydronic module
The pumps that are factory-installed in these units have
motors with efficiency class IE2. The additional electrical data
required* is as follows:
Motors of fixed-speed hydronic module pumps, BW10 (options 116F and 270F)
No.** Description***
BW10 - options 116F and 270F (low-pressure pumps)
20
25
30
35
40
45
50
60
70
80
90
1
Nominal efficiency at full load and nominal voltage
%
80
80
80
80
80
80
80
80
80
80
82
1
Nominal efficiency at 75% rated load and nominal voltage
%
78
78
78
78
78
78
78
78
78
78
82
1
Nominal efficiency at 50% rated load and nominal voltage
%
75
75
75
75
75
75
75
75
75
75
80
2
Efficiency level
IE2
3
Year of manufacture
This information varies depending on the manufacturer and model at the time of
incorporation. Please refer to the motor name plates.
4
Manufacturer's name and trademark, commercial registration
number and place of manufacturer
5
Product's model number
6
Number of motor poles
2
2
2
2
2
2
2
2
2
2
2
7-1
Rated shaft power output at full load and nominal voltage (400 V)
kW
0.66
0.66
0.66
0.66
0.66
0.66
0.66
0.87
0.87
0.87
1.26
7-2
Maximum power input (400 V)****
kW
0.83
0.83
0.83
0.83
0.83
0.83
0.83
1.2
1.2
1.2
1.5
8
Rated input frequency
Hz
50
9-1
Rated voltage
V
3 x 400
9-2
Maximum current drawn (400 V)†
A
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.3
2.3
2.3
3.1
10
Rated speed
r/s
48.2
48.2
48.2
48.2
48.2
48.2
48.2
47.3
47.3
47.3
48.2
rpm 2890
2890
2890
2890
2890
2890
2890
2838
2838
2838
2892
11
Product disassembly, recycling or disposal at end of life
Disassembly using standard tools. Disposal and recycling using an appropriate company.
12
Operating conditions for which the motor is specifically designed
I - Altitudes above sea level
m
< 1000††
II - Ambient air temperature
°C
< 40
IV - Maximum air temperature
Please refer to the operating conditions given in this manual or in the specific conditions in
the selection programs.
V - Potentially explosive atmospheres
Non-ATEX environment
Motors of variable-speed hydronic module pumps, BW10 (options 116J and 270J)
No.** Description***
BW10 - options 116J and 270J (high-pressure pumps)
20
25
30
35
40
45
50
60
70
80
90
1
Nominal efficiency at full load and nominal voltage
%
82
82
82
82
82
82
82
82
82
82
82
1
Nominal efficiency at 75% rated load and nominal voltage
%
82
82
82
82
82
82
82
82
82
82
82
1
Nominal efficiency at 50% rated load and nominal voltage
%
80
80
80
80
80
80
79
79
79
79
79
2
Efficiency level
IE2
3
Year of manufacture
This information varies depending on the manufacturer and model at the time of
incorporation. Please refer to the motor name plates.
4
Manufacturer's name and trademark, commercial registration
number and place of manufacturer
5
Product's model number
6
Number of motor poles
2
2
2
2
2
2
2
2
2
2
2
7-1
Rated shaft power output at full load and nominal voltage (400 V)
kW
1.26
1.26
1.26
1.26
1.26
1.26
1.90
1.90
1.90
1.90
1.90
7-2
Maximum power input (400 V)****
kW
1.50
1.50
1.50
1.50
1.50
1.50
2.30
2.30
2.30
2.30
2.30
8
Rated input frequency
Hz
50
9-1
Rated voltage
V
3 x 400
9-2
Maximum current drawn (400 V)†
A
3.1
3.1
3.1
3.1
3.1
3.1
4.3
4.3
4.3
4.3
4.3
10
Rated speed
r/s
48.2
48.2
48.2
48.2
48.2
48.2
47.7
47.7
47.7
47.7
47.7
rpm 2892
2892
2892
2892
2892
2892
2863
2862
2862
2862
2862
11
Product disassembly, recycling or disposal at end of life
Disassembly using standard tools. Disposal and recycling using an appropriate company.
12
Operating conditions for which the motor is specifically designed
I - Altitudes above sea level
m
< 1000††
II - Ambient air temperature
°C
< 40
IV - Maximum air temperature
Please refer to the operating conditions given in this manual or in the specific conditions in
the selection programs.
V - Potentially explosive atmospheres
Non-ATEX environment
*
Required by regulation 640/2009 with regard to the application of directive 2005/32/EC on the eco-design requirements for electric motors
** Item number imposed by regulation 640/2009, annex I2b.
*** Description given by regulation 640/2009, annex I2b.
**** To obtain the maximum power input for a unit with hydronic module add the maximum unit power input from the electrical data table to the pump power input.
†
To obtain the maximum unit operating current draw for a unit with hydronic module add the maximum unit current draw from the electrical data table to the pump current
draw.
†† Above 1000 m, a degradation of 3% for each 500 m should be taken into consideration.
Содержание BW10 020-090
Страница 30: ...30...
Страница 42: ...VMGFT102...