Installation Guide 

AME 438 SU

Danfoss Heating 

VI.LE.F2.3O 

DH-SMT/SI

ENGLISH

Safety Note

To avoid injury and damage to persons 
and devices, it is absolutely necessary 
these instructions are carefully read 
and observed prior to assembly and 
commissioning. 

Necessary assembly, start-up, and 
maintenance work must be performed 
only by qualified, trained and authorised 
personnel. 

Prior to assembly and maintenance work 
on the controller, the system must be:

- depressurised 
-  cooled down
- emptied 
- cleaned

Please comply with the instructions of the 
system manufacturer or system operator.

Do not remove the cover before the power 

supply is fully switched off.

Disposal instruction

This product should be 

dismantled and its 

components sorted, if 

possible, in various groups 

before recycling or disposal. 

Always follow the local disposal 
regulations.

Mounting actuator

Fix the AME 438 SU on the valve. 

Admissible Installation Positions. 

Dimensions 

Wiring 

❹①

Do not touch anything on the PCB!

Switch off the power line before wiring the 

actuator! Lethal voltage!

Wire the actuator according to the wiring 

diagram.

Control signal

Control signal from the controller must be 
connected to terminals Y (input signal) and 
SN (common) on the AME printed board.

Output signal

Output signal from the terminal X can be 
used for indication of the current position. 
Range depends on the DIP switch settings.

Supply voltage

Supply voltage  
(24 V~ -15 to +10%, 50 Hz) must be 
connected to the terminals SN and SP.

DIP switch settings 

 Factory settings:

ALL switches are on OFF position!

 

U

I

2 V_---V

0 V_---V

Direct

Inverse

---

Sequential

0(2) V_5(6) V

5(6) V_10 V

Proportional

3 point/RL

LOG. flow

LIN. flow

100 % Kvs

Red. Kvs

Reset

Reset

 

Note:

All combinations of DIP switches are 
allowed. All functions that are selected are 
added consecutively. There is only one logic 
override of functionalities i.e. the switch No.6 
Proportional / 3 point, which sets actuator to 
ignore control signal and works as a “simple” 
3-point actuator.

SW1: U/I 

❺①

 

F

actory setting:

voltage control signal (0-10 V).

SW2: 2-10 V / 0-10 V 

❺②

 Factory setting is: 

2-10V.

SW3: Direct/Inverse 

❺③

 Factory setting is: 

DIRECT

SW4:---/Sequential 

❺④

Two actuators can be set to work parallel 
with one control signal. If the SEQUENTIAL 
is set than an actuator responds to split 
control signal (see 0(2)-5(6)V/5(6)-10V).

 

Note:

 

This combination works in combination with 
switch No.5: 0(2)-5(6)V/5(6)-10V

SW5: 0(2)-5(6)V/5(6)-10V 

❺⑤

 

Note:

 

This function is available if switch No.4:  
--- / Sequential is set. 

SW6: Proportional/3 point 

❺⑥

Actuator can operate as “simple” 3-point 
actuator, if the 3-point function is selected. 
Power supply should be connected on SN 
and SP ports 

❹②

. On port 1 or 3 24 VAC 

signal is connected for rising or lowering 
of actuator. Return signal X indicates the 
correct position.

 

Note:

if 3 point function is selected actuator does 
not respond to any control signal on port Y. 
It only rises and lowers spindle if power is 
supplied on port 1 or 3.

SW7: LOG. flow/LIN. flow 

❺⑦

 Factory setting is: 

LOG. Flow (characteristic of valve is 
unchanged)

 

Note:

 

If this function is used in combination with  
non-logarithmic valves the characteristic 
of motorised valve will be anti-logarithm of 
valve’s characteristic (e.g. valve with linear 
characteristic will be transformed to quick 
open characteristic). 

SW8: 100% K

VS

/RED. K

VS

 

❺⑧

 

Note: 

This function works properly only with 
logarithmic (equal percentage) valves.

SW9: Reset 

❺⑨

After the actuator has been connected 
to power supply, the actuator will start 
the self-adjustment procedure. The 
indicator LED flashes until self adjustment 
is finished. The duration depends on the 
spindle travel and will normally last a few 
minutes. The stroke length of the valve is 
stored in the memory after self adjustment 
has been completed. To restart self 
adjustment, change the position of RESET 
switch (switch No.9). If the supply voltage 
is switched off or falls below 80% in more 
than 0.1 s, the current valve position will be 
stored in the memory and all data remain 
saved in the memory also after a power 
supply cut-out.

Содержание AME 438 SU

Страница 1: ...SU www danfoss es P gina 9 SUOMI AME 438 SU www danfoss fi Sivu 11 LIETUVI K AME 438 SU www sildymas danfoss lt Puslapis 13 POLSKI AME 438 SU www danfoss pl Strona 15 AME 438 SU www danfoss ru 17 MAG...

Страница 2: ...2mm 4mm 4mm 5 7 Nm 1 6mm 1 13mm 1 30sec 2 Installation Guide AME 438 SU DH SMT SI VI LE F2 3O Danfoss Heating...

Страница 3: ...0 10 V 3 point 3 3 Installation Guide AME 438 SU Danfoss Heating VI LE F2 3O DH SMT SI...

Страница 4: ...4 Installation Guide AME 438 SU DH SMT SI VI LE F2 3O Danfoss Heating...

Страница 5: ...tuator to ignore control signal and works as a simple 3 point actuator SW1 U I Factory setting voltage control signal 0 10 V SW2 2 10 V 0 10 V Factory setting is 2 10V SW3 Direct Inverse Factory setti...

Страница 6: ...he positioner is in operation or not Moreover the indicator shows the control status and faults Constant light normal operation No light no operation or no power supply Intermittent light 1 Hz self ad...

Страница 7: ...ng Sp ndingssignal 0 10 V SW2 2 10V 0 10V Fabriksindstilling 2 10V SW3 Direkte Indirekte Aktuatoren kan indstilles til nedadg ende spindel ved stigende kontrolsignal DIREKTE Eller opadg ende spindel v...

Страница 8: ...dikerer om aktuatoren er i drift ligesom den viser driftsstatus og eventuelle fejl Konstant lys normal drift Intet lys ikke i drift ingen str mforsyning Interval blink 1Hz selvjusteringsprocedure Inte...

Страница 9: ...ci n La tensi n de alimentaci n 24 V 15 a 10 50 Hz debe conectarse a los terminales SN y SP Configuraci n de los interruptores DIP Ajuste de f brica TODOS los interruptores deben encontrarse en la pos...

Страница 10: ...ser de algunos minutos El recorrido de la v lvula se almacena en la memoria una vez llevado a cabo el proceso de ajuste autom tico Si desea realizar de nuevo el proceso de ajuste autom tico cambie la...

Страница 11: ...V 5 6 V_10 V Verrannollinen 3 piste RL LOG virtaus Lineaarinen virtaus 100 Kvs Pien Kvs Nollaaminen Nollaaminen Huom Kaikki DIP kytkinasetusten yhdistelm t ovat sallittuja Kaikki valitut toiminnot yhd...

Страница 12: ...un itses t toimet on tehty Voit aloittaa itses d n uudelleen muuttamalla NOLLAAMINEN kytkimen asentoa kytkin 9 Jos virransy tt katkeaa tai putoaa alle 80 prosenttiin yli 0 1 sekunnin ajaksi nykyinen v...

Страница 13: ...virk tinis Nuoseklusis 0 2 V_5 6 V 5 6 V_10 V Proporcinis 3 pad i R L LOG srautas LIN srautas 100 Kvs Red Kvs Pradinis nustatymas Pradinis nustatymas Pastaba Leistini visi funkcij pasirinkimo jungikli...

Страница 14: ...ad ti savaiminio nustatymo proced r perjunkite pradinio nustatymo jungikl 9 jungikl Jei maitinimo tampa nutr ksta arba daugiau negu 0 1 s jos reik m b na ma esn nei 80 atmintyje i saugoma esama vo tuv...

Страница 15: ...2 V_5 6 V 5 6 V_10 V Proporcjonalny 3 punktowy RL LOG flow LIN flow 100 Kvs Red Kvs Reset Reset UWAGA Dozwolone s wszystkie kombinacje prze cznik w DIP Wszystkie wybierane funkcje s dodawane sukcesywn...

Страница 16: ...a proces samoregulacji Je eli napi cie zasilaj ce zostanie odci te lub przez okres ponad 0 1 sekundy spadnie poni ej 80 to aktualna pozycja zaworu jest zachowana w pami ci wszystkie dane s zachowywwan...

Страница 17: ...O DH SMT SI Y SN AME DIP 24 15 10 50 SN SP U I 2 V_ V 0 V_ V 0 2 V_5 6 V 5 6 V_10 V 3 RL 100 Kvs Red Kvs DIP OFF DIP 6 SW1 U I 0 10 B AME 438 SU SW2 2 10B 0 10B 2 0 B 4 0 2 10 B SW3 SW4 0 2 5 6 5 6 10...

Страница 18: ...18 Installation Guide AME 438 SU DH SMT SI VI LE F2 3O Danfoss Heating SW7 SW8 100 KVS REDKVS SW9 Reset RESET 9 80 0 1 1 3 20...

Страница 19: ...portional 3 pont R L LOG flow LIN v z tfoly s 100 Kvs Red Kvs Ford tott Vissza ll t s Megjegyz s A mikrokapcsol k helyzeteinek minden kombin ci ja megengedett Minden kiv lasztott funkci egym s ut n ho...

Страница 20: ...ket hossza elt rol sra ker l a mem ri ban Az nbe ll t s jrakezd s hez v ltoztassa meg a RESET mikrokapcsol 9 es kapcsol ll s t Ha a t pfesz lts g lekapcsol dik vagy 0 1 m sodpercn l tov bb 80 al esik...

Страница 21: ...OFF U I 2 V_ V 0 V_ V 0 2 V_5 6 V 5 6 V_10 V Proportional 3 R L LOG flow 100 Kvs Kvs SW1 U I SW2 2 10 V 0 10 V 2V 4mA 0V 0mA 2 10V SW3 SW4 0 2 V 5 6V 5 6 V 10V 5 0 2 V 5 6V 5 6 V 10V SW5 0 2 5 6 V 5 6...

Страница 22: ...unkt RL LOG flow LIN flow 100 Kvs Red Kvs Reset Reset HINWEIS Alle Kombinationen von DIP Schaltern sind erlaubt Gew hlte Funktionen sind hintereinandergelegt Es gibt nur eine logische Umsteuerung der...

Страница 23: ...tanpassungsvorgang kann durch Dr cken der RESET Taste wiederholt werden Schalter No 9 Bei Ausfall der Versorgungsspannung oder beim Absinken auf einen Wert kleiner 80 l nger als 0 1 s wird die aktuell...

Страница 24: ...ssa Ez vonatkozik a m r megrendelt term kekre is felt ve hogy e v ltoztat sok v grehajthat k a m r elfogadott specifik ci l nyeges m dos t sa n lk l Az ebben az anyagban tal lhat v djegyek az rintett...

Отзывы: