U•V6
Instruction Manual
11
|
65
Certified
ISO9001 • VCA
2
INSTALLATION
2.1
Precautions for Use
For your safety, ensure that you are working
on a device that is powered off
before you do
anything!
The housing of the U•V6 unit can be inverted. It can be used in such a way that electric
cables can be inserted from the top, or in such a way that they can be inserted from the
bottom. However, in order to guarantee optimal sealing, it is recommended that you always
insert the cables from the bottom.
The housing of the device is
IP65-
certified and is therefore protected against the presence of
dust and water, provided that the installation instructions are followed.
The housing has a number of machined apertures. You will need to clear these machined
apertures with a flat screwdriver and hammer in order to insert the cable glands.
2.2
Placing the U
•
V6 unit
The U•V6 unit must be placed on a smooth, flat surface. Two fixing systems, a drilling plan
and a quick installation guide are supplied with the device. You can choose to fix the unit
using the housing or the four feet provided.
The housing of the U•V6 unit may only be opened by qualified technicians.
The U•V6 unit must be placed in a room that does not have an explosive atmosphere and
must always be easy to access.
Never place the U•V6 unit, the siren and the detector cables in the vicinity of:
o
high-voltage cables or power cables
o
transmitters or coaxial cables
o
welding stations or frequency regulators.