U•V6
Instruction Manual
44
|
65
Certified
ISO9001 • VCA
Siren output
Not activated
Transistorised output for the siren
The user can confirm their selection by pressing
ENTER
. The system then asks for
confirmation before switching the output.
General fault relay
Ready to activate?
The user can confirm the activation of the selected output by pressing
ENTER
. It is then
activated, along with the equipment that is connected to it.
General fault relay
Activated
The output remains activated for the duration of the output test.
This comes to an end:
▪
upon manual action by user (pressing the
ESC
key).
▪
when the maximum activation time for the output (15 minutes) has expired.
The user may interrupt and cancel the
Output Test
function at any time by pressing
ESC
key. The tests sub-menu is then re-enabled and displays the output test function.
Simulating a Detector
Navigation :
Service menu
→
Tests menu
→
Sensor simulation
A gas-detection simulation can be carried out without disconnecting a detector that is
connected to a measurement channel on the U•V6 unit.
Once the function has been selected, the user must select the detector for which the
simulation should be carried out.
The simulation starts when the detector has been selected:
▪
The initial value for the simulation is the actual gas concentration read by the
detector.
▪
The cursor flashes on the digit being modified (tens or units).
The user can modify the simulated gas-concentration value using the
Up
and
Down
arrow
keys.
The user can use the
Right
and
Left
arrow keys to move from one digit of the gas-
concentration value to the other, with the first digit changing the tens and the second digit
changing the units.
The user can end the simulation by pressing
ESC
.