VRV in General
Si30-408
110
Cases for Examination
1. VRV in General
1.1
Malfunction "E3" is Displayed in Cooling Operation.
Applicable
Models
VRV Plus series (L unit)
Condition
Though an malfunction "E3 (abnormal high-pressure)" is sometimes displayed on the VRV Plus
series (L unit) system, the same condition is not reproduced at the time of inspection
(unintentional operation).
Cause
Electronic expansion valve of the STD outdoor unit 2, which must be opened fully during cooling
operation, is malfunctioning. Since the valve is not opened, pressure for high-pressure use has
exceeded and accutuated the high-pressure switch.
Measure
Recovers by replacing the electronic expansion valve drive coil of the STD outdoor unit 2.
Point of
Diagnosis
When examining multiple outdoor units, do not inspect only the inverter outdoor units but
inspect STD outdoor units 1 and 2.
1.2
Malfunction "F6" is Displayed during Check Operation in
the Winter Season.
Applicable
Models
RX(Y)(Q)
~
M (VRV II series)
Condition
A malfunction "F6" (overcharge of refrigerant) is displayed when a "check operation" is
executed as a test operation under the condition of low outdoor temperature in the winter
season.
Cause
Due to temporary refrigerant mixing into refrigerating oil, misjudgment is made when a "check
operation" is executed under the condition of low outdoor temperature.
Measure
The condition completes by executing the "check operation" again.
Point of
Diagnosis
Be sure to execute a "check operation" with the front panel closed. Or, misjudgment is made
even if the outdoor temperature is low.
Conditions
Possible misjudgment
Low outdoor temperature
F6
High outdoor humidity
E3, E4. UF
Содержание VRV RSXYP16KJY1
Страница 1: ...Si30 408 Basic Training Manual ...
Страница 4: ...Si30 408 ii General Contents ...
Страница 24: ...REFNET Piping Si30 408 20 Introduction ...
Страница 159: ...Si30 408 Collection and Playback of Data on Checker Service Checker Type3 Application Edition 155 Pane fixing ...
Страница 166: ...Collection and Playback of Data on Checker Si30 408 162 Service Checker Type3 Application Edition ...
Страница 171: ...Si30 408 Collection and Playback of Data on Checker Service Checker Type3 Application Edition 167 ...
Страница 172: ...Collection and Playback of Data on Checker Si30 408 168 Service Checker Type3 Application Edition 4 4 Organizing Graph ...
Страница 179: ...Si30 408 Collection and Playback of Data on Checker Service Checker Type3 Application Edition 175 ...
Страница 180: ...Collection and Playback of Data on Checker Si30 408 176 Service Checker Type3 Application Edition ...
Страница 185: ...Si30 408 Points of Analysis Service Checker Type3 Application Edition 181 5 4 Example of Checker Connection ...
Страница 194: ...Points of Analysis Si30 408 190 Service Checker Type3 Application Edition ...
Страница 255: ...Printed in Japan 12 2004 AK ...