Method of Troubleshooting
Si30-408
72
Troubleshooting
3. Method of Troubleshooting
3.1
Excessive / Insufficient Charging of Refrigerant
For VRV system, troubleshooting can be executed only with the operating conditions of air
conditioner relating to pressure control and electronic expansion valve control, and the methods
of judgment are shown below.
1. For excessive charging
(The operating capacity of compressor has a tendency to increase in cooling while decrease
in heating.)
1. Operate with light load by using capacity control of compressor due to increasing of high
pressure (condensing temperature).
(Compressor capacity cannot be controlled to obtain the target pressure.)
As a result, circulation volume of refrigerant decreases, and cooling and heating will
malfunction.
2. In heating operation, since a large amount of liquid refrigerant is stagnant between the
outlet of condenser and the liquid line, the cooling temperature of refrigerant become
large and discharge air temperature lowers even when the target pressure (see below) is
maintained in heating operation. Moreover, the detecting temperature of liquid pipe
thermistor in indoor unit may be kept at approx. 40°C or higher normally, while in this
case, the temperature may lower to approx. 35°C or lower due to a stagnancy of
refrigerant. Accordingly, the discharge temperature may become approx. 30°C.
3. In heating operation, the control is executed during closing operation of EV opening
degree.
Since the liquid pressure rises with the rising high pressure, even if the EV is throttled to
the minimum opening degree (200 pls), refrigerant cannot be super heated at the outlet
of heat exchanger and liquid refrigerant which does not evaporate returns to compressor,
resulting an operation so called "wet operation".
• Superheated degree = 0
→
The discharge pipe temperature lowers.
(Condensing tempe 20°C or less)
2. For insufficient charging
(The operating capacity of compressor has a tendency to decrease in cooling while increase
in heating.)
1. The discharge pipe temperature of compressor rises. (Suction SH increases, and
discharge pipe temperature also increases.)
2. Refrigerant at the outlet of evaporator is superheated. (Electronic expansion valve will be
opened fully.)
In this case, for the suction superheat degree of compressor is increased, alarm display
of insufficient gas (U0) is displayed.
3. In cooling operation, when the operation capacity of compressor is small, since the low
pressure (evaporating pressure) is low against refrigerant load, the unit cannot be
operated with required capacity due to decreasing of refrigerant circulation volume. In
heating operation, it is required to check that the difference between high pressure and
liquid pressure is 0.3 to 0.4 MPa.
Due to the characteristic of expansion valve, refrigerant cannot flow easily when the
pressure difference between inlet and outlet of the valve is 0.2 MPa or more, therefore,
liquid refrigerant will be stagnant between indoor heat exchanger and liquid piping.
Large pressure difference
→
→
→
→
Shortage of refrigerant
Small pressure difference
→
→
→
→
Excessive charge of refrigerant
Target Pressure and Temperature
*
Above target temperature stands for the saturation temperature at gas side.
Target condensing temperature /
High pressure
Target evaporating temperature /
Low pressure
R22
46
°C
1.8MPa
5.5
°C
0.59MPa
R407C
48
°C
1.9MPa
7.5
°C
0.58MPa
R410A
46
°C
2.8MPa
6.0
°C
0.96MPa
Содержание VRV RSXYP16KJY1
Страница 1: ...Si30 408 Basic Training Manual ...
Страница 4: ...Si30 408 ii General Contents ...
Страница 24: ...REFNET Piping Si30 408 20 Introduction ...
Страница 159: ...Si30 408 Collection and Playback of Data on Checker Service Checker Type3 Application Edition 155 Pane fixing ...
Страница 166: ...Collection and Playback of Data on Checker Si30 408 162 Service Checker Type3 Application Edition ...
Страница 171: ...Si30 408 Collection and Playback of Data on Checker Service Checker Type3 Application Edition 167 ...
Страница 172: ...Collection and Playback of Data on Checker Si30 408 168 Service Checker Type3 Application Edition 4 4 Organizing Graph ...
Страница 179: ...Si30 408 Collection and Playback of Data on Checker Service Checker Type3 Application Edition 175 ...
Страница 180: ...Collection and Playback of Data on Checker Si30 408 176 Service Checker Type3 Application Edition ...
Страница 185: ...Si30 408 Points of Analysis Service Checker Type3 Application Edition 181 5 4 Example of Checker Connection ...
Страница 194: ...Points of Analysis Si30 408 190 Service Checker Type3 Application Edition ...
Страница 255: ...Printed in Japan 12 2004 AK ...