Si30-408
HRV-Related
Appendix
245
7.5.4 Multi Function Central Cont Unified On / Off Controller
Proper controller should be selected according to the functions required.
* It is possible to combine the schedule timer.
System Overview
RC1 . . . . . . . . . . . . Central remote controller
RC2 . . . . . . . . . . . . Unified On / Off controller
RSA – D. . . . . . . . . Remote controller for the Indoor unit
R1 – 9 . . . . . . . . . . Remote controller for the HRV unit
System
Description
*1. Independent operation for ventilation is possible, if collective zone interlock setting is "ON"
with the indoor unit in the same zone.
*2. It is possible by the initial setting.
*3. Display of malfunction code only.
*4. The meaning of total evaluation
RSA
[1-00]
R1
A
1
RSB
[1-01]
B
2
RSC
[1-07]
R7
C
7
RSD
[1-08]
D
8
R3
[1-03]
4
[1-02]
3
[1-04]
5
[1-05]
6
R5
R9
[1-10]
10
[1-09]
9
Power
supply
RC2
RC1
Zone setting
(Individual operation
of each group)
Zone setting
(Collective operation for plural group)
Central
transmission line
Central remote controller
Power supply
Unified On / Off controller
Power supply
(HC0039)
–
–
–
–
Total
evaluation
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
*
1
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
*
2
–
–
–
–
–
*
2
–
–
–
–
–
–
–
–
*
3
–
*
3
–
–
–
–
–
–
–
–
–
–
–
*
3
–
–
–
–
–
*
3
–
–
–
–
–
–
–
On Off
Setting
Operation display functions ( means possible)
Choise condition
HRV unit side
Interlocked
operation with
Energy saving
Required ( )
Not Required
Not required
(Setting required
only for
A B
)
Not required
(Setting required
only for
C D
)
Connection required,
when setting
Connection required,
when setting
Connection required,
when setting
Operation / stop
Independent
ventilation
Operation/stop
Ventilation air flow
Ventilation mode
Fresh-up
Group number
setting
for central control
Filter-sign
Malfunction code
*
4
*
5
*
5
AA
AA
AA
BB
CC
DD
AA
AA
CC
DD
(
)
(
)
(
)
Collective by zone
Unit No.
Zone
setting
Interlocked
zone contol
Individual
Collective
RC1
RC2
RSA
– D
R1
– 9
RSA
– D
R1
– 9
RC1
RC2
RSA
– D
R1
– 9
RC1
RC2
RSA
– D
R1
– 9
RC1
RC2
Linked
to A / B
Linked
to C / D
Linked
to A / B
Linked
to C / D
Содержание VRV RSXYP16KJY1
Страница 1: ...Si30 408 Basic Training Manual ...
Страница 4: ...Si30 408 ii General Contents ...
Страница 24: ...REFNET Piping Si30 408 20 Introduction ...
Страница 159: ...Si30 408 Collection and Playback of Data on Checker Service Checker Type3 Application Edition 155 Pane fixing ...
Страница 166: ...Collection and Playback of Data on Checker Si30 408 162 Service Checker Type3 Application Edition ...
Страница 171: ...Si30 408 Collection and Playback of Data on Checker Service Checker Type3 Application Edition 167 ...
Страница 172: ...Collection and Playback of Data on Checker Si30 408 168 Service Checker Type3 Application Edition 4 4 Organizing Graph ...
Страница 179: ...Si30 408 Collection and Playback of Data on Checker Service Checker Type3 Application Edition 175 ...
Страница 180: ...Collection and Playback of Data on Checker Si30 408 176 Service Checker Type3 Application Edition ...
Страница 185: ...Si30 408 Points of Analysis Service Checker Type3 Application Edition 181 5 4 Example of Checker Connection ...
Страница 194: ...Points of Analysis Si30 408 190 Service Checker Type3 Application Edition ...
Страница 255: ...Printed in Japan 12 2004 AK ...