Si30-408
Adaptors for Connection of Air Conditioners
Appendix
213
Caution
The input B is used for forcedly OFF. If this input B is turned ON, the system will be put into
“Stop + Remote controller inhibited”, thus disregarding the input A. Even if the input A is
turned ON with the input B in an OFF state, the content with the input A turned ON will not be
provided. In this case, the input A should be turned ON again.
���
���
���
���
To operate the system using instantaneous input to the input A
Use instantaneous input with ON time of 200 msec or more for the input A.
To conduct demand control using input B
Forcedly thermostat OFF command
This command is to operate the indoor unit only in forcedly fan mode.
Energy saving operation command
This command is to operate the system with set temperature increased by 2°C in cooling
operation or decreased by 2°C in heating operation.
Cautions
While in zone unified control mode, even if a single indoor unit is in operation, the operation
display will be actuated. Consequently, while in last pressing priority mode, some unit stops
operation during the operation display is output.
In this case, even though the input A is turned ON, the system will stop, thus making all units
stop.
���
���
���
���
To operate the system on two input contacts using instantaneous input for the input
A and input B
(Use instantaneous input with ON time of 200 msec or more for the input A.)
Cautions
Using normal input for the input B in Positions 7 to A will put the system into forcedly stop
function (with input A disregarded).
In Position B, the constant input cannot be used for the input B.
Position
Function
Contents of input A
Function of input B
5
Remote
controller
inhibited
Stops if the input A is turned ON while in operation.
Operates if the input A is tuned ON while in stop.
The input B will be put
into forcedly OFF
function mode.
(If the input B is turned
ON, the system will be
put into “Stop + Remote
controller inhibited, Input
A disregarded”.)
6
Last-
pressing
priority
Stops if the input A is turned ON while in operation.
Operates if the input A is tuned ON while in stop.
(The remote controller is permitted at all times.)
Position
Functions & contents with input A turned ON
Functions with input B turned ON
C
Remote controller inhibited
(Same as Position 5)
Forcedly thermostat OFF command
D
Energy saving operation command
E
Last-pressing priority
(Same as Position 6)
Forcedly thermostat OFF command
F
Energy saving operation command
Position
Function
Contents of input A
Contents of input B
7
Remote controller
inhibited
Operation (The remote controller is
inhibited at all the time.)
Stop + Remote
controller inhibited
8
Centralized priority
Ope Remote controller
permitted
9
Remote controller stop
permitted
Ope Only remote controller stop
permitted
(Operation from remote controller is
impossible.)
A
Remote controller
permitted / stop
Only remote controller permitted
(Operation from remote control is
impossible.)
B
Last pressing priority
Operation (The remote controller is
permitted at all the time.)
Stop (The remote
controller is permitted
at all the time.)
Содержание VRV RSXYP16KJY1
Страница 1: ...Si30 408 Basic Training Manual ...
Страница 4: ...Si30 408 ii General Contents ...
Страница 24: ...REFNET Piping Si30 408 20 Introduction ...
Страница 159: ...Si30 408 Collection and Playback of Data on Checker Service Checker Type3 Application Edition 155 Pane fixing ...
Страница 166: ...Collection and Playback of Data on Checker Si30 408 162 Service Checker Type3 Application Edition ...
Страница 171: ...Si30 408 Collection and Playback of Data on Checker Service Checker Type3 Application Edition 167 ...
Страница 172: ...Collection and Playback of Data on Checker Si30 408 168 Service Checker Type3 Application Edition 4 4 Organizing Graph ...
Страница 179: ...Si30 408 Collection and Playback of Data on Checker Service Checker Type3 Application Edition 175 ...
Страница 180: ...Collection and Playback of Data on Checker Si30 408 176 Service Checker Type3 Application Edition ...
Страница 185: ...Si30 408 Points of Analysis Service Checker Type3 Application Edition 181 5 4 Example of Checker Connection ...
Страница 194: ...Points of Analysis Si30 408 190 Service Checker Type3 Application Edition ...
Страница 255: ...Printed in Japan 12 2004 AK ...