Si30-408
Field Settings from Remote Controller
Field Settings from Remote Controller
43
1.1
Field Setting Mode
1.1.1 Settings of
Individual Functions for Indoor Unit
Individual functions of indoor unit can be changed from the remote controller. At the time of
installation or after service inspection/repair, make field settings in accordance with the
following descriptions.
Be noted that wrong settings may result in malfunctions.
(If any optional accessory is mounted to the indoor unit, changes in settings may be needed.
For details, refer to information in the manual for optional accessories.)
Procedure
���
Turn on the power supply.
Turn on the power supply of indoor unit. (Setting is available only with turning on the power
supply.)
Check installation and electric wiring again before turning on the power supply.
(After all LCDs are displayed for turning the power supply, operation is occasionally not
accepted, displaying "88" for a period of about one minute.)
���
Put the system into field setting mode.
While in normal mode, press and hold the
button for a period of four seconds or more
to put the system into "Field Setting Mode".
���
Select mode No.
Select a desired "mode No." using the
button.
���
Select indoor unit No.
While in group control, to make field settings for individual indoor unit (i.e., if mode No. 20,
21, 22, 23 or 25 is selected), press the
button and select the "indoor unit No." to be
set. (Be noted that this operation is not required for the group batch control.)
���
Select setting switch No.
Press the upper button of
and select the "set switch No.".
���
Select setting position No.
Press the lower button of
and select the "set position No.".
���
Determine the content of settings.
Press the
button once and "determine" the content, the setting of which has been
changed.
���
Return to the normal mode.
Press the
button to return the system to "normal mode".
(Example) To set the filter sign time to "Filter Contamination-Heavy" while in group batch
setting mode, set the Mode No. to "10", the Set Switch No. to "0", and the Setting
Position No. to "02".
0-01
1
AIR CONDITIONER
UNIT No.
TEST
(VL042)
3
6
Mode No.
Field Set Mode
7
5
8
2
4
Setting Position No.
Setting Switch No.
20
SETTING
Содержание VRV RSXYP16KJY1
Страница 1: ...Si30 408 Basic Training Manual ...
Страница 4: ...Si30 408 ii General Contents ...
Страница 24: ...REFNET Piping Si30 408 20 Introduction ...
Страница 159: ...Si30 408 Collection and Playback of Data on Checker Service Checker Type3 Application Edition 155 Pane fixing ...
Страница 166: ...Collection and Playback of Data on Checker Si30 408 162 Service Checker Type3 Application Edition ...
Страница 171: ...Si30 408 Collection and Playback of Data on Checker Service Checker Type3 Application Edition 167 ...
Страница 172: ...Collection and Playback of Data on Checker Si30 408 168 Service Checker Type3 Application Edition 4 4 Organizing Graph ...
Страница 179: ...Si30 408 Collection and Playback of Data on Checker Service Checker Type3 Application Edition 175 ...
Страница 180: ...Collection and Playback of Data on Checker Si30 408 176 Service Checker Type3 Application Edition ...
Страница 185: ...Si30 408 Points of Analysis Service Checker Type3 Application Edition 181 5 4 Example of Checker Connection ...
Страница 194: ...Points of Analysis Si30 408 190 Service Checker Type3 Application Edition ...
Страница 255: ...Printed in Japan 12 2004 AK ...