Field Setting on Outdoor Unit
Si30-408
64
Field Settings from Remote Controller
4. Press the RETURN button (BS3) if the refrigerant is charged to the specified capacity. The
operation stops.
[The operation stops automatically in maximum approximately 30 minutes.
If the additional refrigerant charge is not completed within 30 minutes, set the (A) additional
refrigerant charge operation again and start to operate.
If the compressor stops soon after re-operating, the refrigerant could be over charged. The
refrigerant charging is no more available.]
5. Remove the refrigerant charge hose. Then, be sure to open liquid-side stop valve fully
immediately.(Otherwise, the piping could burst due to liquid seal.)
Operating
Condition
Frequency of compressor: 210Hz
Solenoid valve: Open (Y1S, Y2S, Y3S produced before December 2003, Y1S, Y2S
produced after January 2004)
The outdoor fan: High pressure control
The indoor expansion valve (all the rooms): 1024 pls
The indoor fan: H tap
Operating
Procedures
1. Charge the refrigerant normal way first.
Charge from the service port of liquid-side stop valve in stop state of outdoor unit.
(Close fully the liquid and gas side stop valves.)
2. Turn on the power supply of indoor and outdoor units and open the gas side stop valve fully.
(Be sure to close fully the liquid-side stop valve.)
3. Setting of service mode
4. It is completed if the refrigerant is charged to the specified capacity. If the charge is not
completed within 30 minutes, make the setting again and operate
(Pressing the check button in refrigerant additional charging operation stops the operation.)
5. Remove the refrigerant charge hose and open the liquid-side stop valve fully.
* Be sure to operate as the following only if all the refrigerant cannot be charged after trying
the charge in stop state of outdoor unit.
(Otherwise this causes malfunction.)
Press and hold the MODE button for a period of five
seconds while in "Setting mode 1" to put the system into
"Setting mode 2".
8 7 7 7 7 7 7
Press the SET button and set the LED display to the
refrigerant re-filling operation.
8 7 8 7 8 7 7
Press the RETURN button.
8 7 7 7 7 7 9
Press the SET button and set the LED display as shown
in the right figure.
8 7 7 7 7 9 7
Press the RETURN button and the setting is completed.
8 7 7 7 7 8 7
The operation starts when the RETURN button is
pressed again.
8 9 7 7 7 7 7
During operation, the system
displays the pressure level of low
pressure.
0.34MPa
8 8 7 8 8 8 8
0.34MPa
8 8 7 7 8 8 8
0.25MPa
8 8 7 7 7 8 8
0.15MPa
8 8 7 7 7 7 8
When operation is completed. (The system operation
stops within 30 minutes.)
(The display of the immediately previous pressure level
blinks.)
8 8 7 7 7 9 9
This pattern shows that the unit
stopped at pressure level the pressure
level of [0.25MPa or less]
Содержание VRV RSXYP16KJY1
Страница 1: ...Si30 408 Basic Training Manual ...
Страница 4: ...Si30 408 ii General Contents ...
Страница 24: ...REFNET Piping Si30 408 20 Introduction ...
Страница 159: ...Si30 408 Collection and Playback of Data on Checker Service Checker Type3 Application Edition 155 Pane fixing ...
Страница 166: ...Collection and Playback of Data on Checker Si30 408 162 Service Checker Type3 Application Edition ...
Страница 171: ...Si30 408 Collection and Playback of Data on Checker Service Checker Type3 Application Edition 167 ...
Страница 172: ...Collection and Playback of Data on Checker Si30 408 168 Service Checker Type3 Application Edition 4 4 Organizing Graph ...
Страница 179: ...Si30 408 Collection and Playback of Data on Checker Service Checker Type3 Application Edition 175 ...
Страница 180: ...Collection and Playback of Data on Checker Si30 408 176 Service Checker Type3 Application Edition ...
Страница 185: ...Si30 408 Points of Analysis Service Checker Type3 Application Edition 181 5 4 Example of Checker Connection ...
Страница 194: ...Points of Analysis Si30 408 190 Service Checker Type3 Application Edition ...
Страница 255: ...Printed in Japan 12 2004 AK ...