Outdoor Unit Refrigerant System Diagram
SiE 00-07
32
Function R-407C PLUS Series
1. Outdoor Unit Refrigerant System Diagram
1.1
Outdoor Unit Refrigerant System Diagram
RSXYP16~30KJY1
No.
Name
Code
Function
Remarks
A
Inverter compressor
M1C
Combination of a compressor (inverter compressor)
capable of operating at 29-79 Hz with inverter drive and
compressors (constant-speed compressors) operable
only on commercial power supply achieves 45-step control
(38 steps in RSXYP16-20).
B
Constant-speed compressor 1
M2C
C
Constant-speed compressor 2
M3C
(RSXYP24-30 only)
J
Electronic expansion valve
Y1E
(For master unit heat exchangers)
Provides PI control during heating operation to maintain
constant superheated degree (SH).
(Master unit’s left side
exchanger in case of
RSXYP24-30KJY1)
K
Electronic expansion valve
Y2E
(For sub unit heat exchangers)
Provides PI control during heating operation to maintain
constant superheated degree (SH).
(Master unit’s right side heat
exchanger in case of
RSXYP24-30KJY1)
L
Electronic expansion valve
Y3E
(For sub unit’s heat exchanger)
Provides PI control during heating operation to maintain
constant superheated degree (SH).
(RSXYP24-30 only)
M
Solenoid valve
Y1S
(For auxiliary condensers)
N
Solenoid valve
Y2S
(For hot gas bypass and pressure equalization)
Bypasses hot gas during transitional operation such as
defrosting operation to prevent sudden decrease of low
pressure. Also equalizes pressure to reduce startup load.
O
Solenoid valve
Y3S
(For inverter unit liquid injection)
Provides liquid injection to prevent overheating operation.
P
Solenoid valve
Y4S
(For constant-speed unit liquid injection)
Provides liquid injection to prevent overheating operation.
Q
Solenoid valve
Y5S
(For receivers)
R
Solenoid valve
Y6S
(For constant-speed unit liquid injection)
Provides liquid injection to prevent overheating operation.
(RSXYP24-30 only)
S
High pressure sensor
SENPH
Heating operation: Provides PI control for compressors by
detecting high pressure.
Cooling operation: Controls compressors to ensure
sufficient high pressure when outside temperature is low.
T
Low pressure sensor
SENPL
Cooling operation: Provides PI control for compressors by
detecting low pressure.
Heating operation: Controls motorized valves to maintain
constant evaporator superheated degree.
U
High pressure switch
S1PH
Opens at set pressure of 3.09 MPa to stop operation.
V
High pressure switch
S2PH
W
High pressure switch
S3PH
(RSXYP24-30 only)
X
Pressure regulating valve
Pressure relief valve to protect liquid sealing in receiver
piping during transportation or storing.
It opens at 2.65 MPa.
Y
Fusible plug
Plug head melt at 70~75˚C around receiver and high
pressure and high temperature refrigerant is relived.
1
Outside air thermistor
R1T
Detects outside temperature and uses it as a function in
determining defrost IN conditions during heating
operation.
2
Heat exchanger thermistor 1
R2-1(11)T Uses inlet temperature of each heat exchanger as a
function (together with outside temperature data) in
determining defrost IN conditions during heating
operation.
3
Heat exchanger thermistor 2
R2-12T
(RSXYP24-30 only)
4
Heat exchanger thermistor 3
R2-2T
5
Discharge pipe thermistor 1
R3-1(11)T Detects discharge pipe temperature of inverter
compressor and use it for compressor discharge pipe
temperature protection.
6
Discharge pipe thermistor 2
R3-2(12)T Detects discharge pipe temperature of constant-speed
compressor 1 and use it for compressor discharge pipe
temperature protection.
7
Discharge pipe thermistor 3
R3-13T
Detects discharge pipe temperature of constant-speed
compressor 2 and use it for compressor discharge pipe
temperature protection.
(RSXYP24-30 only)
8
Header thermistor 1
R4-1(11)T Detects outlet temperatures of heat exchangers and uses
it in constant superheated degree (SH) control (electronic
expansion valve contro
l)
9
Header thermistor 2
R4-2(12)T
10
Header thermistor 3
R4-13T
(RSXYP24-30 only)
11
Suction pipe thermistor
R6-1T
Detect acumulator outlet temperature and protect
compressor.
Содержание VRV R-407C PLUS Series
Страница 1: ...System R 407C PLUS Series Service Manual SiE 00 07...
Страница 11: ...Introduction SiE 00 07 x...
Страница 17: ...Product Outline SiE 00 07 6 General Information R 407C PLUS Series...
Страница 41: ...Specifications SiE 00 07 30 Specifications R 407C PLUS Series...
Страница 90: ...SiE 00 07 Test Operation Test Operation R 407C PLUS Series 79 1 3 Outdoor Unit PC Board Ass y Outdoor Unit...
Страница 119: ...Test Operation SiE 00 07 108 Test Operation R 407C PLUS Series...
Страница 132: ...SiE 00 07 Troubleshooting by Remote Controller Troubleshooting R 407C PLUS Series 121...