SiE 00-07
Operation Flowcharts
Troubleshooting R-407C PLUS Series
113
Programme dry operation
Programme dry display
Thermostat status?
Fan M1F : 6 minutes stopped
then L operation
Electronic expansion valve Y1E
closed
Drain-up kit M1P : Off after 5
minutes residual operation
Fan M1F : operation: L
Electronic expansion valve Y1E
degree of super heat control
A
(Option)
∗
7
∗
8
(VF023)
ON
OFF
∗
7 Programme dry display
Does not display preset temperature and air flow settings of the controller.
∗
8 Thermostat status
Preset temperature during programme dry operation
Fan in operation
Swing flap
Air flow direction setting
Swing flap?
Fan MF: Operating at set air flow
rate
Electronic expansion valve Y1E
closed
Drain-up kit (M1P): OFF
Auxiliary electric heater (K1R): OFF
Humidifier (Hu): OFF
A
∗
10
∗
11
∗
9
No
YES
Option
(VF024)
∗
9
Fan operation
When fan operation has been selected using the remote controller, operation is turned OFF by
thermostat when temperature control operation has been selected.
∗
10 Air flow direction setting
If fan operation is selected with the remote controller, air discharge is 100% horizontal during
heating.
∗
11 Fan
If fan operation is selected with the remote controller, LL speed operation is carried out during
heating.
Содержание VRV R-407C PLUS Series
Страница 1: ...System R 407C PLUS Series Service Manual SiE 00 07...
Страница 11: ...Introduction SiE 00 07 x...
Страница 17: ...Product Outline SiE 00 07 6 General Information R 407C PLUS Series...
Страница 41: ...Specifications SiE 00 07 30 Specifications R 407C PLUS Series...
Страница 90: ...SiE 00 07 Test Operation Test Operation R 407C PLUS Series 79 1 3 Outdoor Unit PC Board Ass y Outdoor Unit...
Страница 119: ...Test Operation SiE 00 07 108 Test Operation R 407C PLUS Series...
Страница 132: ...SiE 00 07 Troubleshooting by Remote Controller Troubleshooting R 407C PLUS Series 121...