Troubleshooting (Inverter)
SiE 00-07
160
Troubleshooting R-407C PLUS Series
5.2
Outdoor Unit: Inverter Instantaneous Over-Current
Remote Controller
Display
L5
Supposed Causes
Defect of compressor coil (disconnected, defective insulation)
Compressor start-up malfunction (mechanical lock)
Defect of inverter unit
Troubleshooting
Compressor inspection
(VF064)
Inverter
output voltage
check
Inverter output voltage
is not balanced.
(Normal if within
±
8V)
(Note) Must be
measured when
frequency
is stable.
Replace the compressor.
Compressor inspection
Inspect according to the diagnosis
procedure for odd noises, vibration and
operating status of the compressor.
NO
Replace the inverter unit.
YES
YES
Correct power supply.
YES
The compressor's
coil is disconnected or the
insulation is
defective.
NO
NO
Disconnect the connection
between the compressor and
inverter.
There is
instantenious power
drop.