SiE 00-07
Outline of Control (Outdoor Unit)
Function R-407C PLUS Series
61
3.13
Discharge Pipe Temperature Control
Controls the liquid injection and operating frequency to prevent abnormal increase of discharge pipe
temperature and compressor internal temperature.
3.13.1 Liquid Injection Control
Inverter compressor
Opens SVTi (Y3S) (solenoid valve for inverter compressor liquid injection) for 3 minutes after
software startup.
[Cooling]
DSHi: Inverter compressor discharge pipe superheated degree
= Tdi (Th3-1) - (HP equivalent saturation temperature)
Tdi: Inverter compressor discharge pipe temperature (Th3-1)
[Heating]
[Preparing Oil return and defrosting operation (1 min before operation start)]
[Oil return operation/defrosting operation]
SVTi (Y3S) is OFF at any case when inverter compressor stops.
STD compressor
[In cooling operation]
DSHs: STD compressor discharge pipe superheated degree
= Tds1, 2 (Th3-2) - (HP equivalent saturation temperature)
Tds1, 2 : STD compressor discharge pipe temperature (Th3-2)
Normal operation
SVTi : ON
DSHi
≥
40˚C
DSHi<15˚C
(V0826)
OR
&
DSHi<25˚C
10min elapsed
Normal operation
SVTi : ON
•
Tdi
≥
100˚C
•
LP<0.05MPa
•
(HP+0.10) / (LP+0.10)>8
•
Tdi<90˚C
•
LP>0.07MPa
•
2 min elapsed
(V0827)
OR
&
Preparing oil return
and defrosting
SVTi : ON
DSHi
≥
15˚C
Start oil return
& Defrost operation
(V0828)
Normal operation
SVTs1 (Y4S), SVTs2 (Y6S) : ON
10 min
DSHs1, DSHs2
≥
40˚C
DSHs1, DSHs2<15˚C
(V0829)
Содержание VRV R-407C PLUS Series
Страница 1: ...System R 407C PLUS Series Service Manual SiE 00 07...
Страница 11: ...Introduction SiE 00 07 x...
Страница 17: ...Product Outline SiE 00 07 6 General Information R 407C PLUS Series...
Страница 41: ...Specifications SiE 00 07 30 Specifications R 407C PLUS Series...
Страница 90: ...SiE 00 07 Test Operation Test Operation R 407C PLUS Series 79 1 3 Outdoor Unit PC Board Ass y Outdoor Unit...
Страница 119: ...Test Operation SiE 00 07 108 Test Operation R 407C PLUS Series...
Страница 132: ...SiE 00 07 Troubleshooting by Remote Controller Troubleshooting R 407C PLUS Series 121...