Test Operation
SiE 00-07
98
Test Operation R-407C PLUS Series
1.11
Refrigerant Recovery Mode
The electronic expansion valves in the indoor and outdoor units are fixed in the fully open
position for refrigerant recovery.
[Work procedure]
1. Stop equipment operation.
2. Set the service mode.
3. Turn off the power switches of the indoor and outdoor units.
(Turn off the power switch of one unit, then turn off the power switch of the other unit within 10 minutes.)
4. Conduct refrigerant recovery.
5.
Cancel the setting in the setting mode or cancel the mode by conducting power reset of the outdoor
unit.
In service mode 1, press the “MODE” button for 5 seconds to enter
service mode 2.
8 7 7 7 7 7 7
Press the “SET” button to set the LED indicators to the "refrigerant
recovery mode" indication.
8 7 8 7 8 7 8
Press the “RETURN” button.
8 7 7 7 7 7 9
Press the “SET” button to set the LED indicators as shown at right.
8 7 7 7 7 9 7
Press the “RETURN” button to end the setting operation.
8 7 7 7 7 8 7
Press the “RETURN” button again to return to initial status.
8 7 7 7 7 7 7
Содержание VRV R-407C PLUS Series
Страница 1: ...System R 407C PLUS Series Service Manual SiE 00 07...
Страница 11: ...Introduction SiE 00 07 x...
Страница 17: ...Product Outline SiE 00 07 6 General Information R 407C PLUS Series...
Страница 41: ...Specifications SiE 00 07 30 Specifications R 407C PLUS Series...
Страница 90: ...SiE 00 07 Test Operation Test Operation R 407C PLUS Series 79 1 3 Outdoor Unit PC Board Ass y Outdoor Unit...
Страница 119: ...Test Operation SiE 00 07 108 Test Operation R 407C PLUS Series...
Страница 132: ...SiE 00 07 Troubleshooting by Remote Controller Troubleshooting R 407C PLUS Series 121...