Outline of Control (Indoor Unit)
Function R-407C PLUS Series
69
4. Outline of Control (Indoor Unit)
4.1
Drain Pump Control
1. The drain pump is controlled by the ON/OFF buttons (4 button (1) - (4) given in the figure below).
4.1.1
When the Float Switch is Tripped While the Cooling Thermostat is ON:
∗
1. The objective of residual operation is to completely drain any moisture adhering to the fin of the indoor
unit heat exchanger when the thermostat goes off during cooling operation.
4.1.2
When the Float Switch is Tripped During Cooling OFF by Thermostat: