SiUS12-928_A
Control Specification
Function and Control
58
3.13.3 Refrigerant Shortage Control
Outline
I Detecting by power consumption
If the power consumption is below the specified value and the frequency is higher than the
specified frequency, it is regarded as refrigerant shortage.
The power consumption is small comparing with that in the normal operation when refrigerant is
insufficient, and refrigerant shortage is detected by checking a power consumption.
II Detecting by discharge pipe temperature
If the discharge pipe temperature is higher than the target discharge pipe temperature, and the
electronic expansion valve is fully open for more than the specified time, it is regarded as a
refrigerant shortage.
Refer to “Refrigerant shortage” on page 143 for detail.
3.13.4 Anti-icing Function
During cooling, if the heat exchanger temperature in the operation-stopped room lowers more than
the specified temperature for the specified time, the electronic expansion valve is opened in the
operation-stopped room, and fully closed operation is carried out. After this, if freezing abnormality
occurs longer than the specified time, the system shuts down as a system abnormality.
Frequency
Power consumption
Refrigerant shortage zone
40 ~ 55 Hz
(depending on
the model)
(R11685)
Refrigerant shortage
zone
(R1391)
Содержание SUPER MULTI NX G Series
Страница 1: ...SiUS12 928_A Applied Models Inverter Multi Heat Pump G Series J Series...
Страница 7: ...SiUS12 928_A Table of Contents vi...
Страница 10: ...SiUS12 928_A 1 List of Functions Part 1 List of Functions 1 Functions 3...
Страница 11: ...SiUS12 928_A List of Functions 2...
Страница 16: ...SiUS12 928_A 7 Specifications Part 2 Specifications 1 Specifications 9 1 1 Indoor Unit 9 1 2 Outdoor Unit 11...
Страница 17: ...SiUS12 928_A Specifications 8...
Страница 23: ...SiUS12 928_A Specifications Specifications 14...
Страница 25: ...SiUS12 928_A Printed Circuit Board Connector Wiring Diagram 16...
Страница 35: ...SiUS12 928_A Printed Circuit Board Connector Wiring Diagram Printed Circuit Board Connector Wiring Diagram 26...
Страница 37: ...SiUS12 928_A Function and Control 28...
Страница 69: ...SiUS12 928_A Control Specification Function and Control 60...
Страница 71: ...SiUS12 928_A Operation Manual 62...
Страница 73: ...SiUS12 928_A Duct Free System Operation Manual 64 2 Duct Free System 2 1 Remote Controller...
Страница 83: ...SiUS12 928_A Duct Free System Operation Manual 74 2 7 HOME LEAVE Operation is no longer displayed on the LCD...
Страница 84: ...Duct Free System SiUS12 928_A 75 Operation Manual...
Страница 85: ...SiUS12 928_A Duct Free System Operation Manual 76 2 8 TIMER Operation...
Страница 86: ...Duct Free System SiUS12 928_A 77 Operation Manual...
Страница 87: ...SiUS12 928_A Duct Free System Operation Manual 78 2 9 Note for Multi System...
Страница 88: ...Duct Free System SiUS12 928_A 79 Operation Manual...
Страница 97: ...SiUS12 928_A Slim Duct Built In System Operation Manual 88...
Страница 99: ...SiUS12 928_A Service Diagnosis 90...
Страница 169: ...SiUS12 928_A Removal Procedure 160...
Страница 225: ...SiUS12 928_A Trial Operation and Field Settings 216...
Страница 235: ...SiUS12 928_A Appendix 226...
Страница 243: ...SiUS12 928_A Wiring Diagrams Appendix 234...