Control Specification
SiUS12-928_A
53
Function and Control
3.11 Low Hz High Pressure Limit
Outline
The upper limit of high pressure in a low Hz zone is set. The upper limit of the indoor heat
exchanger temperature is also set by the operating frequency. There are 3 zones. Reset zone,
keep zone, and dropping zone, and the frequency control is carried out according to each zone.
Detail
Note:
Dropping: The system stops 2 minutes after staying in the dropping zone.
3.12 Electronic Expansion Valve Control
Outline
The following items are included in the electronic expansion valve control.
Electronic expansion valve is fully closed
1. Electronic expansion valve is fully closed when turning on the power.
2. Pressure equalizing control
Room Distribution Control
1. Gas pipe isothermal control
2. SC (subcooling) control
3. Liquid pipe temperature control (with all ports connected and all rooms being air-conditioned)
4. Liquid pipe temperature control for stopped rooms
5. Condensation prevention control for indoor motor
Open Control
1. Electronic expansion valve control when starting operation
2. Electronic expansion valve control when frequency is changed
3. Electronic expansion valve control for defrosting
4. Electronic expansion valve control for oil recovery
5. Electronic expansion valve control when a discharge pipe temperature is abnormally high
6. Electronic expansion valve control when the discharge pipe thermistor is disconnected
7. Electronic expansion valve control for indoor unit freeze-up protection
Feedback Control
1. Discharge pipe temperature control
18 class
24/32 class
60°C (140°F)
57°C (135°F)
59°C (138°F)
56°C (133°F)
56°C (133°F)
53°C (127°F)
Highest indoor
heat exchanger
temperat
u
re
among the
operating room
(R12297)
Dropping zone
Содержание SUPER MULTI NX G Series
Страница 1: ...SiUS12 928_A Applied Models Inverter Multi Heat Pump G Series J Series...
Страница 7: ...SiUS12 928_A Table of Contents vi...
Страница 10: ...SiUS12 928_A 1 List of Functions Part 1 List of Functions 1 Functions 3...
Страница 11: ...SiUS12 928_A List of Functions 2...
Страница 16: ...SiUS12 928_A 7 Specifications Part 2 Specifications 1 Specifications 9 1 1 Indoor Unit 9 1 2 Outdoor Unit 11...
Страница 17: ...SiUS12 928_A Specifications 8...
Страница 23: ...SiUS12 928_A Specifications Specifications 14...
Страница 25: ...SiUS12 928_A Printed Circuit Board Connector Wiring Diagram 16...
Страница 35: ...SiUS12 928_A Printed Circuit Board Connector Wiring Diagram Printed Circuit Board Connector Wiring Diagram 26...
Страница 37: ...SiUS12 928_A Function and Control 28...
Страница 69: ...SiUS12 928_A Control Specification Function and Control 60...
Страница 71: ...SiUS12 928_A Operation Manual 62...
Страница 73: ...SiUS12 928_A Duct Free System Operation Manual 64 2 Duct Free System 2 1 Remote Controller...
Страница 83: ...SiUS12 928_A Duct Free System Operation Manual 74 2 7 HOME LEAVE Operation is no longer displayed on the LCD...
Страница 84: ...Duct Free System SiUS12 928_A 75 Operation Manual...
Страница 85: ...SiUS12 928_A Duct Free System Operation Manual 76 2 8 TIMER Operation...
Страница 86: ...Duct Free System SiUS12 928_A 77 Operation Manual...
Страница 87: ...SiUS12 928_A Duct Free System Operation Manual 78 2 9 Note for Multi System...
Страница 88: ...Duct Free System SiUS12 928_A 79 Operation Manual...
Страница 97: ...SiUS12 928_A Slim Duct Built In System Operation Manual 88...
Страница 99: ...SiUS12 928_A Service Diagnosis 90...
Страница 169: ...SiUS12 928_A Removal Procedure 160...
Страница 225: ...SiUS12 928_A Trial Operation and Field Settings 216...
Страница 235: ...SiUS12 928_A Appendix 226...
Страница 243: ...SiUS12 928_A Wiring Diagrams Appendix 234...