SiUS12-928_A
Troubleshooting
Service Diagnosis
126
5.18 Compressor Sensor System Abnormality (24/32 Class)
Remote
Controller
Display
H0
Outdoor Unit LED
Display
A
5
1
4
2
4
3
1
4
1
Method of
Malfunction
Detection
Fault condition is identified by the supply voltage and the DC voltage which is detected before
the compressor startup.
Fault condition is identified by the compressor current which is detected right after the
compressor startup.
If the error repeats 16 times, the system is shut down.
Reset condition: Continuous run for about 5 minutes without any other error
Malfunction
Decision
Conditions
The detected value of the supply voltage and the DC voltage is obviously low or high.
The compressor current does not run when the compressor is started.
Supposed
Causes
Disconnection of reactor
Disconnection of compressor
Defective outdoor unit PCB
Defective compressor
Содержание SUPER MULTI NX G Series
Страница 1: ...SiUS12 928_A Applied Models Inverter Multi Heat Pump G Series J Series...
Страница 7: ...SiUS12 928_A Table of Contents vi...
Страница 10: ...SiUS12 928_A 1 List of Functions Part 1 List of Functions 1 Functions 3...
Страница 11: ...SiUS12 928_A List of Functions 2...
Страница 16: ...SiUS12 928_A 7 Specifications Part 2 Specifications 1 Specifications 9 1 1 Indoor Unit 9 1 2 Outdoor Unit 11...
Страница 17: ...SiUS12 928_A Specifications 8...
Страница 23: ...SiUS12 928_A Specifications Specifications 14...
Страница 25: ...SiUS12 928_A Printed Circuit Board Connector Wiring Diagram 16...
Страница 35: ...SiUS12 928_A Printed Circuit Board Connector Wiring Diagram Printed Circuit Board Connector Wiring Diagram 26...
Страница 37: ...SiUS12 928_A Function and Control 28...
Страница 69: ...SiUS12 928_A Control Specification Function and Control 60...
Страница 71: ...SiUS12 928_A Operation Manual 62...
Страница 73: ...SiUS12 928_A Duct Free System Operation Manual 64 2 Duct Free System 2 1 Remote Controller...
Страница 83: ...SiUS12 928_A Duct Free System Operation Manual 74 2 7 HOME LEAVE Operation is no longer displayed on the LCD...
Страница 84: ...Duct Free System SiUS12 928_A 75 Operation Manual...
Страница 85: ...SiUS12 928_A Duct Free System Operation Manual 76 2 8 TIMER Operation...
Страница 86: ...Duct Free System SiUS12 928_A 77 Operation Manual...
Страница 87: ...SiUS12 928_A Duct Free System Operation Manual 78 2 9 Note for Multi System...
Страница 88: ...Duct Free System SiUS12 928_A 79 Operation Manual...
Страница 97: ...SiUS12 928_A Slim Duct Built In System Operation Manual 88...
Страница 99: ...SiUS12 928_A Service Diagnosis 90...
Страница 169: ...SiUS12 928_A Removal Procedure 160...
Страница 225: ...SiUS12 928_A Trial Operation and Field Settings 216...
Страница 235: ...SiUS12 928_A Appendix 226...
Страница 243: ...SiUS12 928_A Wiring Diagrams Appendix 234...