SiUS12-928_A
Troubleshooting
Service Diagnosis
112
5.8
Unspecified Voltage (between Indoor and Outdoor Units)
Remote
Controller
Display
UA
Method of
Malfunction
Detection
The supply power is detected for its requirements (different from pair type and multi type) by the
indoor / outdoor transmission signal.
Malfunction
Decision
Conditions
The pair type and multi type are interconnected.
Supposed
Causes
Wrong models interconnected
Wrong wiring of connecting wires
Wrong indoor unit PCB or outdoor unit PCB mounted
Defective indoor unit PCB
Defective outdoor unit PCB
Troubleshooting
(R11707)
Caution
NO
YES
YES
YES
NO
NO
Check the code numbers
(2P01234, for example) of the
indoor and outdoor unit PCB with
the Parts List.
Match the compatible models.
Change for the correct PCB.
Replace the indoor unit PCB
(or the outdoor unit PCB).
OK?
Matched compatibly?
Correct the connection.
Are the
connection wires connected
property?
Check the
combination of the
indoor
and outdoor unit.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Содержание SUPER MULTI NX G Series
Страница 1: ...SiUS12 928_A Applied Models Inverter Multi Heat Pump G Series J Series...
Страница 7: ...SiUS12 928_A Table of Contents vi...
Страница 10: ...SiUS12 928_A 1 List of Functions Part 1 List of Functions 1 Functions 3...
Страница 11: ...SiUS12 928_A List of Functions 2...
Страница 16: ...SiUS12 928_A 7 Specifications Part 2 Specifications 1 Specifications 9 1 1 Indoor Unit 9 1 2 Outdoor Unit 11...
Страница 17: ...SiUS12 928_A Specifications 8...
Страница 23: ...SiUS12 928_A Specifications Specifications 14...
Страница 25: ...SiUS12 928_A Printed Circuit Board Connector Wiring Diagram 16...
Страница 35: ...SiUS12 928_A Printed Circuit Board Connector Wiring Diagram Printed Circuit Board Connector Wiring Diagram 26...
Страница 37: ...SiUS12 928_A Function and Control 28...
Страница 69: ...SiUS12 928_A Control Specification Function and Control 60...
Страница 71: ...SiUS12 928_A Operation Manual 62...
Страница 73: ...SiUS12 928_A Duct Free System Operation Manual 64 2 Duct Free System 2 1 Remote Controller...
Страница 83: ...SiUS12 928_A Duct Free System Operation Manual 74 2 7 HOME LEAVE Operation is no longer displayed on the LCD...
Страница 84: ...Duct Free System SiUS12 928_A 75 Operation Manual...
Страница 85: ...SiUS12 928_A Duct Free System Operation Manual 76 2 8 TIMER Operation...
Страница 86: ...Duct Free System SiUS12 928_A 77 Operation Manual...
Страница 87: ...SiUS12 928_A Duct Free System Operation Manual 78 2 9 Note for Multi System...
Страница 88: ...Duct Free System SiUS12 928_A 79 Operation Manual...
Страница 97: ...SiUS12 928_A Slim Duct Built In System Operation Manual 88...
Страница 99: ...SiUS12 928_A Service Diagnosis 90...
Страница 169: ...SiUS12 928_A Removal Procedure 160...
Страница 225: ...SiUS12 928_A Trial Operation and Field Settings 216...
Страница 235: ...SiUS12 928_A Appendix 226...
Страница 243: ...SiUS12 928_A Wiring Diagrams Appendix 234...