SiEN04-306D
Troubleshooting
Service Diagnosis
137
Troubleshooting
Check No.4
Refer to P.139
Check No.6
Refer to P.141
Reconnect in position.
Open the stop valve.
Repair the pipe flare or
replace the square union.
Check the power transistor
harness for looseness.
Correct it as required. Also
replace cracked pipe if any.
Check the pipes for
improper contact. Correct
as required. Also replace
cracked pipe if any.
Replace the electronic
expansion valve.
CT in trouble (refer to H8).
Replace the room
temperature or outdoor air
thermistor, or the indoor
unit or outdoor unit heat
exchanger thermistor.
(1) Replace the PCB.
(2) Replace the compressor.
Procedure complete
(R2853)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Any thermistor
disconnected?
YES
Malfunctioning
Malfunctioning
NO
Functioning
Stop valve closed?
NO
YES
Check the CT.
YES
NO
Gas shortage error again?
Functioning
C
heck No.
6
Check the thermistors.
YES
NO
Oil oozing at internal piping?
NO
YES
C
heck No.
4
Electronic expansion valve
functioning?
YES
NO
Oil oozing at relay pipe
connections?
Check for gas leakage.
Change for a specified amount of
fresh refrigerant.
NO
YES
Compressor vibrating
too much?
* Discharge pipe thermistor
* Indoor / outdoor unit heat exchanger thermistor
* Room temperature thermistor
* Outdoor air thermistor
Содержание SiEN04-306D
Страница 109: ...Instruction SiEN04 306D 100 System Configuration...
Страница 199: ...Outdoor Unit SiEN04 306D 190 Removal Procedure...
Страница 200: ...SiEN04 306D Others 191 Part 8 Others 1 Others 192 1 1 Test Run from the remote control 192 1 2 Jumper Settings 193...
Страница 203: ...Others SiEN04 306D 194 Others...
Страница 214: ...SiEN04 306D Wiring Diagrams Appendix 205 FTKD18 24 28BVMS...
Страница 216: ...SiEN04 306D Wiring Diagrams Appendix 207 RKD18 24 28BVMS...
Страница 217: ...Wiring Diagrams SiEN04 306D 208 Appendix...