ESIE05-03
Outdoor Unit Functional Concept
Part 2 – Functional Description
2–51
3
2
4
5
1
3.3.6
Suction Pipe Superheat Protection Control (Heating Mode)
Outline
In case the suction superheat value in heating mode is too high, the oil return to the compressor will
be insufficient. In order to avoid that the compressor oil will be accumulated in the outdoor unit heat
exchanger, the upper limit frequency will be decreased.
Flow chart
Normal operation
Lowering upper limit
frequency for 1-step
every 20 seconds
Raising upper limit
frequency for 1-step
every 20 seconds
• Suction SH > 12°C
• Suction SH > 10°C
• EV opening degree = 480pls
• Suction SH > 12°C
• Suction SH > 10°C
• EV opening degree = 480pls
• Suction SH < 10°C
• EV opening degree < 450pls
• Suction SH < 8°C
• Suction SH < 6°C
• Suction SH < 6°C
• Upper limit frequency = Maximum frequency
• Suction SH < 8°C
• Suction SH < 10°C
• EV opening degree < 450 pls
OR
OR
OR
OR
&
&
&
• &
•OR
• &
ESIE05-03.book Page 51 Wednesday, April 6, 2005 4:09 PM
Содержание RZQ100B7W1B
Страница 1: ...Service Manual ESIE05 03 RZQ71 125B8V3B RZQ100 140B7W1B Sky Air Inverter R 410A B series...
Страница 2: ......
Страница 10: ...ESIE05 03 viii Table of Contents 3 1 4 5...
Страница 24: ...ESIE05 03 1 2 Part 1 System Outline 3 1 1 5...
Страница 32: ...General Outline Outdoor Units ESIE05 03 1 10 Part 1 System Outline 3 1 1 4 5...
Страница 42: ...Specifications ESIE05 03 1 20 Part 1 System Outline 3 1 1 4 5...
Страница 56: ...Functional Diagrams ESIE05 03 1 34 Part 1 System Outline 3 1 1 4 5...
Страница 58: ...ESIE05 03 1 36 Part 1 System Outline...
Страница 70: ...Wiring Diagrams ESIE05 03 1 48 Part 1 System Outline 3 1 1 4 5...
Страница 84: ...PCB Layout ESIE05 03 1 62 Part 1 System Outline 3 1 1 4 5...
Страница 86: ...ESIE05 03 2 2 Part 2 Functional Description 3 1 2 5...
Страница 110: ...General Functionality ESIE05 03 2 26 Part 2 Functional Description 3 1 2 4 5...
Страница 150: ...ESIE05 03 3 2 Part 3 Troubleshooting 3 1 3 5...
Страница 188: ...Troubleshooting ESIE05 03 3 40 Part 3 Troubleshooting 3 1 3 4 5...
Страница 264: ...Additional Checks for Troubleshooting ESIE05 03 3 116 Part 3 Troubleshooting 3 1 3 4 5...
Страница 266: ...ESIE05 03 4 2 Part 4 Commissioning and Test Run 3 1 4 5...
Страница 306: ...ESIE05 03 5 2 Part 5 Disassembly and Maintenance 3 1 5...
Страница 320: ...Disassembly and Maintenance Outdoor Units ESIE05 03 5 16 Part 5 Disassembly and Maintenance 3 1 5 5...