Control Specification
SiBE041213E
39
Function and Control
3.4
Discharge Pipe Temperature Control
Outline
The discharge pipe temperature is used as the internal temperature of the compressor. If the
discharge pipe temperature rises above a certain level, the upper limit of frequency is set to
keep the discharge pipe temperature from rising further.
Detail
Zone
Control
Stop zone
When the temperature reaches the stop zone, the compressor stops.
Dropping zone
The upper limit of frequency decreases.
Keep zone
The upper limit of frequency is kept.
Up zone
The upper limit of frequency increases.
Reset zone
The upper limit of frequency is canceled.
35 class
42 class
50 class
A
(ºC)
110
110
110
B
(ºC)
105
103
103
C
(ºC)
101
102
101.5
D
(ºC)
99
100
100
E
(ºC)
97
95
95
(R14642)
Discharge pipe
temperature
Stop zone
Dropping zone
Keep zone
Up zone
Reset zone
E
˚C
A
˚C
B
˚C
C
˚C
D
˚C
Содержание RXS35K2V1B
Страница 12: ...SiBE041213E 1 List of Functions Part 1 List of Functions 1 Functions 2 ...
Страница 14: ...SiBE041213E 3 Specifications Part 2 Specifications 1 Specifications 4 ...
Страница 59: ...SiBE041213E Remote Controller 48 Part 5 Remote Controller 1 Remote Controller 49 ...
Страница 111: ...SiBE041213E Check Service Diagnosis 100 42 class 50 class R12266 Tester 1 2 3 4 Tester 1 2 3 4 R14700 ...
Страница 113: ...SiBE041213E Check Service Diagnosis 102 42 class 50 class R18241 Power module Power module R16692 ...
Страница 129: ...Revision History Month Year Version Revised contents 05 2013 SiBE041213E First edition ...