Main Functions
SiBE041213E
21
Function and Control
1.7
Thermostat Control
Outline
Thermostat control is based on the difference between the room thermistor temperature and the
target temperature.
Detail
Thermostat OFF Condition
The temperature difference is in the zone A.
Thermostat ON Condition
The temperature difference returns to the zone C after being in the zone A.
The system resumes from defrost control in any zones except A.
The operation turns on in any zones except A.
The monitoring time has passed while the temperature difference is in the zone B.
(Cooling / Dry: 10 minutes, Heating: 10 seconds)
<Cooling / Dry>
<Heating>
Refer to “Temperature Control” on page 15 for detail.
B
A
OFF
ON
C
Room thermistor temperature – target temperature
–1.5
°
C
(R12319)
Cooling: –0.5
°
C
Dry: –0.5
°
C
Cooling: –2.0
°
C
Dry: –2.5 ~ –2.0
°
C
OFF
OFF
ON
ON
B
A
C
1.5˚C
2.0˚C
0.5˚C
Room thermistor temperature – target temperature
(R11894)
Содержание RXS35K2V1B
Страница 12: ...SiBE041213E 1 List of Functions Part 1 List of Functions 1 Functions 2 ...
Страница 14: ...SiBE041213E 3 Specifications Part 2 Specifications 1 Specifications 4 ...
Страница 59: ...SiBE041213E Remote Controller 48 Part 5 Remote Controller 1 Remote Controller 49 ...
Страница 111: ...SiBE041213E Check Service Diagnosis 100 42 class 50 class R12266 Tester 1 2 3 4 Tester 1 2 3 4 R14700 ...
Страница 113: ...SiBE041213E Check Service Diagnosis 102 42 class 50 class R18241 Power module Power module R16692 ...
Страница 129: ...Revision History Month Year Version Revised contents 05 2013 SiBE041213E First edition ...